| 2018-02-14 08:23:19 | 1ST REVIEW: FBC 2017 6TH EDITION |
| | |
| | GAS COMMENTS: |
| | |
| | 1. THE DEVELOPED LENGTH TO TH FURTHEST APPLIANCE ON THE |
| | GAS RISER ADDS UP TO 165' UNDER THE GAS RISER NOTES IT |
| | IS LISTED AT 150 PLEASE CLARIFY. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 2. THE SIZING TABLES ARE LISTED UNDER THE FBC 2014 THE |
| | CURRENT CODE IS THE FBC FG 2017 PLEASE CORRECT ON PLAN. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 3. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND |
| | TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE |
| | SEC. 502 THRU 505. |
| | |
| | 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS AND |
| | INSTALLATION GUIDES FOR ALL GAS EQUIPMENT AND |
| | REGULATORS TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| | NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 |
| | |
| | 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE |
| | FBC-2014 FUEL GAS CODE SEC. 304. |
| | |
| | 6. THE FUTURE POOL HEATER IS MISSING FROM THE GAS LOAD |
| | CALCULATIONS PLEASE CLARIFY. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 7. THE BBQ GRILLE IS SHOWN AS 100,000 ON THE GAS RISER |
| | AND IS LISTED AS 75,000 ON THE GAS LOAD CALCULATION |
| | PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 8. THE FUTURE GENERATOR IS SHOWN AS 22,100 ON THE RISER |
| | AND 221,000 ON THE GAS LOAD CALCULATION PLEASE CLARIFY. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 9. THE TANKLESS WATER HEATER IS SHOWN AS 199,000 ON THE |
| | RISER AND 130,000 ON THE GAS LOAD CALCULATION PLEASE |
| | CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 10. THE TOTAL GAS LOAD CALCULATION I CAME UP WITH IS |
| | 1,320,000 THE PLAN SHOWS 826,00 PLEASE CLARIFY. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 11. THE RISER IS SHOWING THE BRANCH TO THE WATER |
| | HEATER, DRYER AND FIRE PLACE AS UNDERGROUND PE WITCH IS |
| | NOT ALLOWED UNDER STRUCTURES THE FLOOR PLAN SHOWS ABOVE |
| | CLG SCH 40 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 12. SHOW THE TRANSITION FROM PE TO SCH 40 ABOVE THE |
| | GROUND AT THE FIRST BRANCH. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 13. THE CONNECTION FOR THE GENERATOR SHALL BE A MIN. OF |
| | 3/4 ON THE .05LB SIDE OF THE REGULATOR. PER FBC FG |
| | TABLE 402.4(2) |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |