Plan Review Notes
Plan Review Notes For Permit 18010592
Permit Number 18010592
Review Stop E
Sequence Number 1
Notes
Date Text
2018-02-09 07:17:44FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E-1
  
 LAUNDRY AREA
  
 GFCI PROTECTION AND ARC FAULT PROTECTION REQUIRED IN
 THIS AREA.
  
 E3902.9 LAUNDRY AREAS.
 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES
 INSTALLED IN LAUNDRY AREAS SHALL HAVE GROUND-FAULT
 CIRCUIT INTERRUPTER PROTECTION FOR PERSONNEL.
 [210.8(A)(9)]
 E3902.16 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION.
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS,
 BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE PROTECTED BY ANY OF THE FOLLOWING: [210.12(A)]
  
  
 KITCHEN
  
 GFCI PROTECTION AND ARC FAULT PROTECTION REQUIRED IN
 THIS AREA.
 COUNTER ON LEFT SIDE NEEDS OUTLETS PER CODE 210.52
 DISHWASHER NEEDS TO BE GFCI PROTECTED.
  
 E3902.6 KITCHEN RECEPTACLES.
 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES
 THAT SERVE COUNTERTOP SURFACES SHALL HAVE GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL.
 [210.8(A)(6)]
 E3902.16 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION.
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS,
 BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE PROTECTED BY ANY OF THE FOLLOWING: [210.12(A)]
 E3902.10 KITCHEN DISHWASHER BRANCH CIRCUIT.
 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION SHALL BE
 PROVIDED FOR OUTLETS THAT SUPPLY DISHWASHERS IN
 DWELLING UNIT LOCATIONS. [210.8(D)]
 E3901.4 COUNTERTOP RECEPTACLES.
 IN KITCHENS PANTRIES, BREAKFAST ROOMS, DINING ROOMS AND
 SIMILAR AREAS OF DWELLING UNITS, RECEPTACLE OUTLETS FOR
 COUNTERTOP SPACES SHALL BE INSTALLED IN ACCORDANCE WITH
 SECTIONS E3901.4.1 THROUGH E3901.4.5
  
  
 OUTDOOR PATIO (GRILL AREA)
  
 GFCI PROTECTION ON ALL 15 AND 20A OUTLETS INSTALLED
 OUTSIDE.
  
 E3902.3 OUTDOOR RECEPTACLES.
 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES
 INSTALLED OUTDOORS SHALL HAVE GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL.
 [210.8(A)(3)]
  
  
  
 MEDIA ROOM
  
 OUTLET SPACING DOES NOT APPEAR TO MEET CODE
 E3901.2.1 SPACING.
 RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL
 SPACE IS MORE THAN 6 FEET (1829 MM), FROM A RECEPTACLE
 OUTLET. [210.52(A)(1)]
  
  
  
 GARAGE
  
 DOOR OPENERS TO BE GFCI PROTECTED
  
 E3902.2 GARAGE AND ACCESSORY BUILDING RECEPTACLES.
 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE RECEPTACLES
 INSTALLED IN GARAGES AND GRADE-LEVEL PORTIONS OF
 UNFINISHED ACCESSORY BUILDINGS USED FOR STORAGE OR WORK
 AREAS SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER
 PROTECTION FOR PERSONNEL. [210.8(A)(2)]
  
 BATH #2
  
 NO OUTLET INSTALLED
  
 E3901.6 BATHROOM.
 AT LEAST ONE WALL RECEPTACLE OUTLET SHALL BE INSTALLED
 IN BATHROOMS AND SUCH OUTLET SHALL BE LOCATED WITHIN 36
 INCHES (914 MM) OF THE OUTSIDE EDGE OF EACH LAVATORY
 BASIN. THE RECEPTACLE OUTLET SHALL BE LOCATED ON A WALL
 OR PARTITION THAT IS ADJACENT TO THE LAVATORY BASIN
 LOCATION, LOCATED ON THE COUNTERTOP, OR INSTALLED ON
 THE SIDE OR FACE OF THE BASIN CABINET. THE RECEPTACLE
 SHALL BE LOCATED NOT MORE THAN 12 INCHES (305 MM) BELOW
 THE TOP OF THE BASIN. RECEPTACLE OUTLETS SHALL NOT BE
 INSTALLED IN A FACE-UP POSITION IN THE WORK SURFACES OR
 COUNTERTOPS IN A BATHROOM BASIN LOCATION. RECEPTACLE
 OUTLET ASSEMBLIES INSTALLED IN COUNTERTOPS SHALL BE
 LISTED FOR THE APPLICATION. [210.52(
  
  
 1ST AND 2ND FLOOR
  
 SMOKE ALARMS AND CO ALARM REQUIRED R314, R315
  
 PAGE -E-2
  
 BATH #1
  
 NEEDS A LIGHT AND SWITCH AT EXTERIOR DOOR.
  
 E3903.3 ADDITIONAL LOCATIONS.
 AT LEAST ONE WALL-SWITCH-CONTROLLED LIGHTING OUTLET
 SHALL BE INSTALLED IN HALLWAYS, STAIRWAYS, ATTACHED
 GARAGES, AND DETACHED GARAGES WITH ELECTRIC POWER. AT
 LEAST ONE WALL-SWITCH-CONTROLLED LIGHTING OUTLET SHALL
 BE INSTALLED TO PROVIDE ILLUMINATION ON THE EXTERIOR
 SIDE OF EACH OUTDOOR EGRESS DOOR HAVING GRADE LEVEL
 ACCESS, INCLUDING OUTDOOR EGRESS DOORS FOR ATTACHED
 GARAGES AND DETACHED GARAGES WITH ELECTRIC POWER. A
 VEHICLE DOOR IN A GARAGE SHALL NOT BE CONSIDERED AS AN
 OUTDOOR EGRESS DOOR. WHERE ONE OR MORE LIGHTING OUTLETS
 ARE INSTALLED FOR INTERIOR STAIRWAYS, THERE SHALL BE A
 WALL SWITCH AT EACH FLOOR LEVEL AND LANDING LEVEL THAT
 INCLUDES AN ENTRYWAY TO CONTROL THE LIGHTING OUTLETS
 WHERE THE STAIRWAY BETWEEN FLOOR LEVELS HAS SIX OR MORE
 RISERS. [210.70(A)(2)]
  
  
  
  
 PAGE E-5
  
 RISER DIAGRAM SHOWS 1/0 ON 200A MAIN AS A FEED TO PANEL
 "B"
  
 E3603.1.2 UNGROUNDED FEEDER CONDUCTORS.
 FOR A FEEDER RATED AT 100 THROUGH 400 AMPERES, THE
 FEEDER CONDUCTORS SUPPLYING THE ENTIRE LOAD ASSOCIATED
 WITH A ONE-FAMILY DWELLING, OR THE FEEDER CONDUCTORS
 SUPPLYING THE ENTIRE LOAD ASSOCIATED WITH AN INDIVIDUAL
 DWELLING UNIT IN A TWO-FAMILY DWELLING, SHALL HAVE AN
 AMPACITY OF NOT LESS THAN 83 PERCENT OF THE FEEDER
 RATING
  
 NEED INTER SYSTEM BONDING STRIP 250.94
  
 E3609.3 BONDING FOR OTHER SYSTEMS.
 AN INTERSYSTEM BONDING TERMINATION FOR CONNECTING
 INTERSYSTEM BONDING CONDUCTORS REQUIRED FOR OTHER
 SYSTEMS SHALL BE PROVIDED EXTERNAL TO ENCLOSURES AT THE
 SERVICE EQUIPMENT OR METERING EQUIPMENT ENCLOSURE AND
 AT THE DISCONNECTING MEANS FOR ANY ADDITIONAL BUILDINGS
 OR STRUCTURES.
  
  
 NOTES HAVE REFERENCES TO 2008 AND 2011 CODES WE ARE
 USING THE 2014 NEC.
  