| 2018-02-09 07:17:44 | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | PAGE E-1 |
| | |
| | LAUNDRY AREA |
| | |
| | GFCI PROTECTION AND ARC FAULT PROTECTION REQUIRED IN |
| | THIS AREA. |
| | |
| | E3902.9 LAUNDRY AREAS. |
| | 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES |
| | INSTALLED IN LAUNDRY AREAS SHALL HAVE GROUND-FAULT |
| | CIRCUIT INTERRUPTER PROTECTION FOR PERSONNEL. |
| | [210.8(A)(9)] |
| | E3902.16 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION. |
| | BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- |
| | AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY |
| | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, |
| | DENS, |
| | BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| | SHALL BE PROTECTED BY ANY OF THE FOLLOWING: [210.12(A)] |
| | |
| | |
| | KITCHEN |
| | |
| | GFCI PROTECTION AND ARC FAULT PROTECTION REQUIRED IN |
| | THIS AREA. |
| | COUNTER ON LEFT SIDE NEEDS OUTLETS PER CODE 210.52 |
| | DISHWASHER NEEDS TO BE GFCI PROTECTED. |
| | |
| | E3902.6 KITCHEN RECEPTACLES. |
| | 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES |
| | THAT SERVE COUNTERTOP SURFACES SHALL HAVE GROUND-FAULT |
| | CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL. |
| | [210.8(A)(6)] |
| | E3902.16 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION. |
| | BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- |
| | AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY |
| | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, |
| | DENS, |
| | BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| | SHALL BE PROTECTED BY ANY OF THE FOLLOWING: [210.12(A)] |
| | E3902.10 KITCHEN DISHWASHER BRANCH CIRCUIT. |
| | GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION SHALL BE |
| | PROVIDED FOR OUTLETS THAT SUPPLY DISHWASHERS IN |
| | DWELLING UNIT LOCATIONS. [210.8(D)] |
| | E3901.4 COUNTERTOP RECEPTACLES. |
| | IN KITCHENS PANTRIES, BREAKFAST ROOMS, DINING ROOMS AND |
| | SIMILAR AREAS OF DWELLING UNITS, RECEPTACLE OUTLETS FOR |
| | COUNTERTOP SPACES SHALL BE INSTALLED IN ACCORDANCE WITH |
| | SECTIONS E3901.4.1 THROUGH E3901.4.5 |
| | |
| | |
| | OUTDOOR PATIO (GRILL AREA) |
| | |
| | GFCI PROTECTION ON ALL 15 AND 20A OUTLETS INSTALLED |
| | OUTSIDE. |
| | |
| | E3902.3 OUTDOOR RECEPTACLES. |
| | 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES |
| | INSTALLED OUTDOORS SHALL HAVE GROUND-FAULT |
| | CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL. |
| | [210.8(A)(3)] |
| | |
| | |
| | |
| | MEDIA ROOM |
| | |
| | OUTLET SPACING DOES NOT APPEAR TO MEET CODE |
| | E3901.2.1 SPACING. |
| | RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT |
| | MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL |
| | SPACE IS MORE THAN 6 FEET (1829 MM), FROM A RECEPTACLE |
| | OUTLET. [210.52(A)(1)] |
| | |
| | |
| | |
| | GARAGE |
| | |
| | DOOR OPENERS TO BE GFCI PROTECTED |
| | |
| | E3902.2 GARAGE AND ACCESSORY BUILDING RECEPTACLES. |
| | 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE RECEPTACLES |
| | INSTALLED IN GARAGES AND GRADE-LEVEL PORTIONS OF |
| | UNFINISHED ACCESSORY BUILDINGS USED FOR STORAGE OR WORK |
| | AREAS SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER |
| | PROTECTION FOR PERSONNEL. [210.8(A)(2)] |
| | |
| | BATH #2 |
| | |
| | NO OUTLET INSTALLED |
| | |
| | E3901.6 BATHROOM. |
| | AT LEAST ONE WALL RECEPTACLE OUTLET SHALL BE INSTALLED |
| | IN BATHROOMS AND SUCH OUTLET SHALL BE LOCATED WITHIN 36 |
| | INCHES (914 MM) OF THE OUTSIDE EDGE OF EACH LAVATORY |
| | BASIN. THE RECEPTACLE OUTLET SHALL BE LOCATED ON A WALL |
| | OR PARTITION THAT IS ADJACENT TO THE LAVATORY BASIN |
| | LOCATION, LOCATED ON THE COUNTERTOP, OR INSTALLED ON |
| | THE SIDE OR FACE OF THE BASIN CABINET. THE RECEPTACLE |
| | SHALL BE LOCATED NOT MORE THAN 12 INCHES (305 MM) BELOW |
| | THE TOP OF THE BASIN. RECEPTACLE OUTLETS SHALL NOT BE |
| | INSTALLED IN A FACE-UP POSITION IN THE WORK SURFACES OR |
| | COUNTERTOPS IN A BATHROOM BASIN LOCATION. RECEPTACLE |
| | OUTLET ASSEMBLIES INSTALLED IN COUNTERTOPS SHALL BE |
| | LISTED FOR THE APPLICATION. [210.52( |
| | |
| | |
| | 1ST AND 2ND FLOOR |
| | |
| | SMOKE ALARMS AND CO ALARM REQUIRED R314, R315 |
| | |
| | PAGE -E-2 |
| | |
| | BATH #1 |
| | |
| | NEEDS A LIGHT AND SWITCH AT EXTERIOR DOOR. |
| | |
| | E3903.3 ADDITIONAL LOCATIONS. |
| | AT LEAST ONE WALL-SWITCH-CONTROLLED LIGHTING OUTLET |
| | SHALL BE INSTALLED IN HALLWAYS, STAIRWAYS, ATTACHED |
| | GARAGES, AND DETACHED GARAGES WITH ELECTRIC POWER. AT |
| | LEAST ONE WALL-SWITCH-CONTROLLED LIGHTING OUTLET SHALL |
| | BE INSTALLED TO PROVIDE ILLUMINATION ON THE EXTERIOR |
| | SIDE OF EACH OUTDOOR EGRESS DOOR HAVING GRADE LEVEL |
| | ACCESS, INCLUDING OUTDOOR EGRESS DOORS FOR ATTACHED |
| | GARAGES AND DETACHED GARAGES WITH ELECTRIC POWER. A |
| | VEHICLE DOOR IN A GARAGE SHALL NOT BE CONSIDERED AS AN |
| | OUTDOOR EGRESS DOOR. WHERE ONE OR MORE LIGHTING OUTLETS |
| | ARE INSTALLED FOR INTERIOR STAIRWAYS, THERE SHALL BE A |
| | WALL SWITCH AT EACH FLOOR LEVEL AND LANDING LEVEL THAT |
| | INCLUDES AN ENTRYWAY TO CONTROL THE LIGHTING OUTLETS |
| | WHERE THE STAIRWAY BETWEEN FLOOR LEVELS HAS SIX OR MORE |
| | RISERS. [210.70(A)(2)] |
| | |
| | |
| | |
| | |
| | PAGE E-5 |
| | |
| | RISER DIAGRAM SHOWS 1/0 ON 200A MAIN AS A FEED TO PANEL |
| | "B" |
| | |
| | E3603.1.2 UNGROUNDED FEEDER CONDUCTORS. |
| | FOR A FEEDER RATED AT 100 THROUGH 400 AMPERES, THE |
| | FEEDER CONDUCTORS SUPPLYING THE ENTIRE LOAD ASSOCIATED |
| | WITH A ONE-FAMILY DWELLING, OR THE FEEDER CONDUCTORS |
| | SUPPLYING THE ENTIRE LOAD ASSOCIATED WITH AN INDIVIDUAL |
| | DWELLING UNIT IN A TWO-FAMILY DWELLING, SHALL HAVE AN |
| | AMPACITY OF NOT LESS THAN 83 PERCENT OF THE FEEDER |
| | RATING |
| | |
| | NEED INTER SYSTEM BONDING STRIP 250.94 |
| | |
| | E3609.3 BONDING FOR OTHER SYSTEMS. |
| | AN INTERSYSTEM BONDING TERMINATION FOR CONNECTING |
| | INTERSYSTEM BONDING CONDUCTORS REQUIRED FOR OTHER |
| | SYSTEMS SHALL BE PROVIDED EXTERNAL TO ENCLOSURES AT THE |
| | SERVICE EQUIPMENT OR METERING EQUIPMENT ENCLOSURE AND |
| | AT THE DISCONNECTING MEANS FOR ANY ADDITIONAL BUILDINGS |
| | OR STRUCTURES. |
| | |
| | |
| | NOTES HAVE REFERENCES TO 2008 AND 2011 CODES WE ARE |
| | USING THE 2014 NEC. |
| | |