| 2018-01-22 09:38:02 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. |
| | CODE: FBC 6TH EDITION (2017) |
| | |
| | 1- FLAT ROOF: |
| | A) NEED TO PROVIDE CURRENT FLORIDA PRODUCT APPROVAL (2 |
| | COPIES) . FLORIDA PRODUCT APPROVAL SUBMITTED IS FOR THE |
| | 2014 EDITION. THE CURRENT CODE IS THE FBC 6TH EDITION |
| | (2017). FAC 61G20-3.001. |
| | |
| | B) CLEARLY MARK ON THE PRODUCT APPROVAL WHICH APPROVED |
| | ASSEMBLY IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE |
| | WITH THE DESIGN PRESSURES OF SEC. R301.1 FBC-6TH |
| | EDITION (2017). NOTE: IF THE SELECTED ASSEMBLY DOESN'T |
| | MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN NEED |
| | TO PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS |
| | REQUIRED BY NOTE #4 ON PAGE 1 OF 3 OF FLORIDA PRODUCT |
| | APPROVAL SUBMITTED. |
| | |
| | C) VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS (EVEN |
| | FOR OWNER BUILDERS) AS REQUIRED BY SEC. 109.3 CITY |
| | AMENDMENTS. SPECIFY THE TOTAL SHINGLES AREA TO BE |
| | REPLACED AND THE TOTAL FLAT ROOF AREA TO BE REPLACED TO |
| | ADJUST THE VALUE AS REQUIRED BY CITY ROOFING POLICY. |
| | |
| | D) SPECIFY THE SHINGLES ROOF PITCH TO VERIFY COMPLIANCE |
| | WITH SEC. R905.2.2 FBC-RESIDENTIAL. |
| | |
| | 2- OWNER IS REQUESTING AN OWNER BUILDER PERMIT. NEED TO |
| | SUBMIT OWNER/BUILDER DISCLOSURE STATEMENT. SEC. 489.103 |
| | FLORIDA STATUTES. ASK PERMIT CLERK FOR PROPER FORM TO |
| | BE COMPLETED. AND, CLARIFY WHY THE HOUSE IS NOT |
| | HOMESTEADED IN FLORIDA AND THE OWNER'S ADDRESS IS |
| | LOCATED IN ANOTHER STATE. |
| | |