2018-04-09 17:43:02ASSEMBLY (A2), BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017).
  
 1- THE OCCUPANT LOAD CALCULATION ON SHEET 1.5A WAS
 REVISED. NEED TO COMPLY WITH THE MINIMUM 5% SEATING
 SPACES AS REQUIRED BY SEC. 226.1 OF FBC-ACCESSIBILITY
 CODE.
 (NOTE: THIS ISSUE WAS DISCUSSED AND CLARIFIED WITH PETE
 RUSSO ON 04/18/18).
  
 2- NUMBER OF PEOPLE SHOWN IN THE OCCUPANT LOAD
 CALCULATION ON SHEET 1.5A DOESN'T MATCH NUMBER OF
 PEOPLE SHOWN ON LIFE SAFETY NOTE #11 ON SAME SHEET.
 ALSO, IT DOESN'T MATCH NUMBER OF PEOPLE SHOWN ON SHEET
 C-1. REVISE ALL NUMBERS AS REQUIRED TO MATCH. SEC.
 107.2.1 CITY AMENDMENTS.
  
 3- NUMBER OF SEATS SHOWN IN THE OCCUPANT LOAD
 CALCULATION ON SHEET 1.5A DOESN'T MATCH NUMBER OF SEATS
 SHOWN ON SHEET C-1. REVISE AS REQUIRED TO MATCH. SEC.
 107.2.1 CITY AMENDMENTS.
  
 4- FLOOR PLAN ON SHEET 1.0A IS INCOMPLETE. IT DOESN'T
 SHOW THE FRONT WALL AND REAR WALL. PROVIDE COMPLETE
 DRAWING. SEC. 107.2.1 CITY AMENDMENTS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DON' T STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
 BUILDING DATA:
 BUILDING TYPE: III-B
 OCCUPANCY: A-2
 S. F. 2180
 OCC. LOAD: ?????
 RESTROOMS: 2