Plan Review Notes
Plan Review Notes For Permit 18010561
Permit Number 18010561
Review Stop M
Sequence Number 2
Notes
Date Text
2018-03-13 14:49:572ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18010561
 3/13/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 4.0M: THE REVISED PLAN IS INDICATING
 RECIRCULATION OF AIR FROM THE KITCHEN INTO THE DINING
 ROOM AND COUNTER AREA WHICH IS PROHIBITED PER FOOTNOTE
 B, TABLE 403.1.1.
  
 2) 4.0M: INDICATE HOW THE 246 CFMS OF COMBUSTION FOR
 THE APPLIANCES AIR WAS CALCULATED, AND HOW THE AIR IS
 BEING PROVIDED- SECTION 304 FBC-14 FBC-17 FUEL GAS.
  
 3) ADVISORY:CONCERNING THE FUTURE KITCHEN HOOD EXHAUST
 SYSTEM, PLEASE REVIEW SECTION C403.2.8 FBC-17 ENERGY
 CONSERVATION AS IT MAY IMPACT THE HVAC SYSTEMS.
  
 C403.2.8 KITCHEN EXHAUST SYSTEMS.
  
 REPLACEMENT AIR INTRODUCED DIRECTLY INTO THE EXHAUST
 HOOD CAVITY SHALL NOT BE GREATER THAN 10 PERCENT OF THE
 HOOD EXHAUST AIRFLOW RATE. CONDITIONED SUPPLY AIR
 DELIVERED TO ANY SPACE SHALL NOT EXCEED THE GREATER OF
 THE FOLLOWING:
  
 1.THE VENTILATION RATE REQUIRED TO MEET THE SPACE
 HEATING OR COOLING LOAD.
  
 2.THE HOOD EXHAUST FLOW MINUS THE AVAILABLE TRANSFER
 AIR FROM ADJACENT SPACE WHERE AVAILABLE TRANSFER AIR IS
 CONSIDERED THAT PORTION OF OUTDOOR VENTILATION AIR NOT
 REQUIRED TO SATISFY OTHER EXHAUST NEEDS, SUCH AS
 RESTROOMS, AND NOT REQUIRED TO MAINTAIN PRESSURIZATION
 OF ADJACENT SPACES.
  
 WHERE TOTAL KITCHEN HOOD EXHAUST AIRFLOW RATE IS
 GREATER THAN 5,000 CFM (2360 L/S), EACH HOOD SHALL BE A
 FACTORY BUILT COMMERCIAL EXHAUST HOOD LISTED BY A
 NATIONALLY RECOGNIZED TESTING LABORATORY IN COMPLIANCE
 WITH UL 710. EACH HOOD SHALL HAVE A MAXIMUM EXHAUST
 RATE AS SPECIFIED IN TABLE C403.2.8 AND SHALL COMPLY
 WITH ONE OF THE FOLLOWING:
  
 1.NOT LESS THAN 50 PERCENT OF ALL REPLACEMENT AIR SHALL
 BE TRANSFER AIR THAT WOULD OTHERWISE BE EXHAUSTED.
  
 2.DEMAND VENTILATION SYSTEMS ON NOT LESS THAN 75
 PERCENT OF THE EXHAUST AIR THAT ARE CAPABLE OF NOT LESS
 THAN A 50-PERCENT REDUCTION IN EXHAUST AND REPLACEMENT
 AIR SYSTEM AIRFLOW RATES, INCLUDING CONTROLS NECESSARY
 TO MODULATE AIRFLOW IN RESPONSE TO APPLIANCE OPERATION
 AND TO MAINTAIN FULL CAPTURE AND CONTAINMENT OF SMOKE,
 EFFLUENT AND COMBUSTION PRODUCTS DURING COOKING AND
 IDLE.
  
 3.LISTED ENERGY RECOVERY DEVICES WITH A SENSIBLE HEAT
 RECOVERY EFFECTIVENESS OF NOT LESS THAN 40 PERCENT ON
 NOT LESS THAN 50 PERCENT OF THE TOTAL EXHAUST AIRFLOW.
  
 WHERE A SINGLE HOOD, OR HOOD SECTION, IS INSTALLED OVER
 APPLIANCES WITH DIFFERENT DUTY RATINGS, THE MAXIMUM
 ALLOWABLE FLOW RATE FOR THE HOOD OR HOOD SECTION SHALL
 BE BASED ON THE REQUIREMENTS FOR THE HIGHEST APPLIANCE
 DUTY RATING UNDER THE HOOD OR HOOD SECTION.
  
 EXCEPTION: WHERE NOT LESS THAN 75 PERCENT OF ALL THE
 REPLACEMENT AIR IS TRANSFER AIR THAT WOULD OTHERWISE BE
 EXHAUSTED
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved