| Date |
Text |
| 2018-03-19 18:29:32 | 03/19/2018 2ND GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE TOTAL BTU IS 883 ON ISOMETRIC, IF YOU ADD UP GAS |
| | LOAD CALCULATION I COME UP WITH 848 BUT YOUR TOTAL SAYS |
| | 818, WHICH ONE IS THE CORRECT LOAD. PLEASE ADDRESS THIS |
| | AS IT IS THE SECOND REQUEST FOR CLARIFICATION. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | 2. THERE WAS A REQUEST FOR MANUFACTURES SPECIFICATION |
| | SHEET FOR ALL GAS EQUIPMENT AND ON YOUR REPLY LETTER, |
| | IT STATES IT HAS BEEN INCLUDED BUT CANNOT FIND IT AS |
| | THIS IS A SECOND REQUEST TO DO A REVIEW ON THIS GAS. |
| | NFPA 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 |
| | 3. THERE ARE 2 NEW CONVENTIONAL OVENS AT 70 BTU ADDED |
| | TO THE NEW SUBMITTED PLAN WE WILL ALSO NEED |
| | SPECIFICATIONS FOR IT. PER WPB AMEND TO FBC 107.2.1 |
| | 4. 15. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION. PROVIDE DOCUMENTATION FROM THE |
| | MANUFACTURER THAT THE REGULATORS ARE APPROVED FOR |
| | EXTERIOR USE. 2017 FBC FUEL GAS SEC.410.1. |
| | 5. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| | USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| | THE GAS CODE OR ANOTHER STANDARD THAT WAS USED IN THE |
| | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC FUEL |
| | GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4 |
| | (1) THRU 402.4 (37). |
| | 6. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| | SHALL BE ONSITE AT THE TIME OF INSPECTION 2017 FBC FUEL |
| | GAS SEC. 402.2 AND 301.3 |
| | |
| | LUIS A. CRESPO |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |
| | [email protected] |
| | 561-805-6720 |
| | |