| Plan Review Notes For Permit 18010561 |
| Permit Number |
18010561 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-03-09 11:14:15 | PERMIT # 18010561 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | 2ND REVIEW | | | FAIL COMMENT: | | | | | | 1) REPEAT COMMENT - - SHEET 1.5A - OCCUPANT LOAD | | | CALCULATION: THERE ARE DISCREPANCIES REGARDING THE | | | LISTED OCCUPANCY LOAD CALCULATIONS AND THE DETAILS | | | PROVIDED IN THE DRAWING. BASED ON SQUARE FOOTAGE OF | | | SEATING AREA (BENCH AND NON-FIXED) THE TOTAL SEATING | | | COUNT SHOULD BE 33 PERSONS. PLEASE PROVIDE | | | JUSTIFICATION REGARDING DISCREPANCY IN OCCUPANCY LOAD | | | CALCULATION FOR NON-FIXED SEATING AND ACTUAL SEATING | | | PROVIDED. | | | TOTAL OCCUPANT LOAD FOR THIS LOCATION IS 59 PERSONS, AS | | | LISTED ON SHEET C-1. HOWEVER, SEATING IS FOR 33 | | | PERSONS, NOT 40, AS INCORRECTLY LISTED ON SHEET C-1. | | | | | | ALL PREVIOUS COMMENTS HAVE BEEN ADDRESSED. | | | | | | | | | SUE ELLEN CALDERON | | | ASSISTANT FIRE MARSHAL | | | [email protected] | | | |
|