2018-03-09 11:14:15PERMIT # 18010561
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 2ND REVIEW
 FAIL COMMENT:
  
 1) REPEAT COMMENT - - SHEET 1.5A - OCCUPANT LOAD
 CALCULATION: THERE ARE DISCREPANCIES REGARDING THE
 LISTED OCCUPANCY LOAD CALCULATIONS AND THE DETAILS
 PROVIDED IN THE DRAWING. BASED ON SQUARE FOOTAGE OF
 SEATING AREA (BENCH AND NON-FIXED) THE TOTAL SEATING
 COUNT SHOULD BE 33 PERSONS. PLEASE PROVIDE
 JUSTIFICATION REGARDING DISCREPANCY IN OCCUPANCY LOAD
 CALCULATION FOR NON-FIXED SEATING AND ACTUAL SEATING
 PROVIDED.
 TOTAL OCCUPANT LOAD FOR THIS LOCATION IS 59 PERSONS, AS
 LISTED ON SHEET C-1. HOWEVER, SEATING IS FOR 33
 PERSONS, NOT 40, AS INCORRECTLY LISTED ON SHEET C-1.
  
 ALL PREVIOUS COMMENTS HAVE BEEN ADDRESSED.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL