| 2018-02-12 12:35:22 | 1ST REVIEW: FBC 2017 6TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. PLEASE PROVIDE CALCULATIONS FOR THE EXISTING GREASE |
| | INTERCEPTOR WITH EXISTING LOAD AND THE NEW LOAD. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | 2. PROVIDE NOTE ON PLAN A SEPARATE PERMIT REQUIRED FOR |
| | BACKFLOW. PER WPB UTILITIES DEPT. |
| | |
| | 3. THE NEW BACK FLOW SHALL BE INSTALLED NEXT TO METER. |
| | PER WPB CROSS CONNECTION MANUAL |
| | |
| | 4. SHT. 3.0P PLUMBING NOTE #1 THE CURRENT CODE SHALL BE |
| | 2017 6TH EDITION FBC |
| | |
| | 5. BOTH OF THE PLUMBING SHEETS ARE LABELED 3.0P PLEASE |
| | CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 6. THE SANITARY ISOMETRIC DOES NOT MATCH THE FLOOR PLAN |
| | IT SHOWS THE 2 AND 3 COMPARTMENT SINKS DRAINING |
| | TOGETHER INTO THE SAME FLOOR SINK THE FLOOR PLAN SHOW |
| | THEM ACROSS THE KITCHEN DRAINING INTO TWO SEPARATE |
| | FLOOR SINKS PLEASE CLARIFY. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 7. THE WATER ISOMETRIC DOES NOT MATCH THE FLOOR PLAN |
| | THE ISO SHOWS A 50 GAL WATER HEATER THE FLOOR PLAN |
| | SHOWS A TANKLESS AND THE 3 COMPARTMENT SINK IS MISSING |
| | PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 8. SHOW ON THE WATER ISOMETRIC, VALVES ON ALL THE DROPS |
| | AND AIR HAMMER ARRESTORS PER FBC PL 604.9 , 606.1 (5) |
| | |
| | 9. SHOW TRAP PRIMER ON FLOOR DRAINS. PER FBC PL |
| | 1002.4.1 |
| | |
| | 10. PLACE NOTE ON THE PLAN TEMPERED WATER SHALL BE |
| | DELIVERED FROM LAVATORIES AND GROUP WASH FIXTURES |
| | LOCATED IN PUBLIC TOILET FACILITIES PROVIDED FOR |
| | CUSTOMERS, PATRONS AND VISITORS. TEMPERED WATER SHALL |
| | BE DELIVERED THROUGH AN APPROVED WATER-TEMPERATURE |
| | LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA |
| | B125.3. PER FBC PL 416.5 |
| | |
| | 11. THE EXISTING GREASE INTERCEPTOR IS SHOWN AS 1000 |
| | GAL ON FIRST PLUMB PAGE AND AS 1150 ON THE SANITARY |
| | ISOMETRIC DRAWING PLEASE CLARIFY. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |