Plan Review Notes
Plan Review Notes For Permit 18010561
Permit Number 18010561
Review Stop P
Sequence Number 1
Notes
Date Text
2018-02-12 12:35:221ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE CALCULATIONS FOR THE EXISTING GREASE
 INTERCEPTOR WITH EXISTING LOAD AND THE NEW LOAD. PER
 WPB AMEND TO FBC 107.2.1
  
 2. PROVIDE NOTE ON PLAN A SEPARATE PERMIT REQUIRED FOR
 BACKFLOW. PER WPB UTILITIES DEPT.
  
 3. THE NEW BACK FLOW SHALL BE INSTALLED NEXT TO METER.
 PER WPB CROSS CONNECTION MANUAL
  
 4. SHT. 3.0P PLUMBING NOTE #1 THE CURRENT CODE SHALL BE
 2017 6TH EDITION FBC
  
 5. BOTH OF THE PLUMBING SHEETS ARE LABELED 3.0P PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 6. THE SANITARY ISOMETRIC DOES NOT MATCH THE FLOOR PLAN
 IT SHOWS THE 2 AND 3 COMPARTMENT SINKS DRAINING
 TOGETHER INTO THE SAME FLOOR SINK THE FLOOR PLAN SHOW
 THEM ACROSS THE KITCHEN DRAINING INTO TWO SEPARATE
 FLOOR SINKS PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 7. THE WATER ISOMETRIC DOES NOT MATCH THE FLOOR PLAN
 THE ISO SHOWS A 50 GAL WATER HEATER THE FLOOR PLAN
 SHOWS A TANKLESS AND THE 3 COMPARTMENT SINK IS MISSING
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 8. SHOW ON THE WATER ISOMETRIC, VALVES ON ALL THE DROPS
 AND AIR HAMMER ARRESTORS PER FBC PL 604.9 , 606.1 (5)
  
 9. SHOW TRAP PRIMER ON FLOOR DRAINS. PER FBC PL
 1002.4.1
  
 10. PLACE NOTE ON THE PLAN TEMPERED WATER SHALL BE
 DELIVERED FROM LAVATORIES AND GROUP WASH FIXTURES
 LOCATED IN PUBLIC TOILET FACILITIES PROVIDED FOR
 CUSTOMERS, PATRONS AND VISITORS. TEMPERED WATER SHALL
 BE DELIVERED THROUGH AN APPROVED WATER-TEMPERATURE
 LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA
 B125.3. PER FBC PL 416.5
  
 11. THE EXISTING GREASE INTERCEPTOR IS SHOWN AS 1000
 GAL ON FIRST PLUMB PAGE AND AS 1150 ON THE SANITARY
 ISOMETRIC DRAWING PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  