| 2018-01-30 09:34:02 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18010561 |
| | 1/30/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS 4.0M & 4.1M: PLEASE CORRECT THE NOTE ON SHEET |
| | 4.1M THAT STATES " (2) EXISTING 10-TON PACKAGED UNITS |
| | SHALL BE REPLACED WITH NEW HIGH EFFICIENCY UNITS (1) |
| | 5-TON & (1) 7.5-TON". THERE IS NO NEW 7.5 TON SYSTEM |
| | SHOWN ON THE PLAN OR IN THE SCHEDULE. |
| | |
| | 2) 4.1M: VERIFY THE THE ROOF STAND INSTALLATION DESIGN |
| | WILL WITHSTAND 170 MPH WIND SPEED AND ASSOCIATED |
| | LATERAL AND UPLIFT PRESSURES. THE PLAN DESIGN IS |
| | INDICATING 140 MPH. |
| | |
| | 3) THE MECHANICAL PLANS FOR THE RESTAURANT SHALL BE IN |
| | COMPLIANCE WITH SECTION 508.1.2 AIR BALANCE: |
| | |
| | DESIGN PLANS FOR A FACILITY WITH A COMMERCIAL KITCHEN |
| | VENTILATION SYSTEM SHALL INCLUDE A SCHEDULE OR DIAGRAM |
| | INDICATING THE DESIGN OUTDOOR AIR BALANCE. THE DESIGN |
| | OUTDOOR AIR BALANCE SHALL INDICATE ALL EXHAUST AND |
| | REPLACEMENT AIR FOR THE FACILITY, PLUS THE NET |
| | EXFILTRATION IF APPLICABLE. THE TOTAL REPLACEMENT AIR |
| | AIRFLOW RATE SHALL EQUAL THE TOTAL EXHAUST AIRFLOW RATE |
| | PLUS THE NET EXFILTRATION. |
| | |
| | 4) SUBMIT TWO COPIES OF THE NOA FOR THE RMS AC ROOF |
| | STAND. |
| | |
| | 5) ADVISORY: SEPARATE PERMITS ARE REQUIRED FOR KITCHEN |
| | HOODS, FIRE SUPRESSION SYSTEMS, AND WALK IN COOLERS AND |
| | FREEZERS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |