2018-01-30 09:34:021ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18010561
 1/30/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS 4.0M & 4.1M: PLEASE CORRECT THE NOTE ON SHEET
 4.1M THAT STATES " (2) EXISTING 10-TON PACKAGED UNITS
 SHALL BE REPLACED WITH NEW HIGH EFFICIENCY UNITS (1)
 5-TON & (1) 7.5-TON". THERE IS NO NEW 7.5 TON SYSTEM
 SHOWN ON THE PLAN OR IN THE SCHEDULE.
  
 2) 4.1M: VERIFY THE THE ROOF STAND INSTALLATION DESIGN
 WILL WITHSTAND 170 MPH WIND SPEED AND ASSOCIATED
 LATERAL AND UPLIFT PRESSURES. THE PLAN DESIGN IS
 INDICATING 140 MPH.
  
 3) THE MECHANICAL PLANS FOR THE RESTAURANT SHALL BE IN
 COMPLIANCE WITH SECTION 508.1.2 AIR BALANCE:
  
 DESIGN PLANS FOR A FACILITY WITH A COMMERCIAL KITCHEN
 VENTILATION SYSTEM SHALL INCLUDE A SCHEDULE OR DIAGRAM
 INDICATING THE DESIGN OUTDOOR AIR BALANCE. THE DESIGN
 OUTDOOR AIR BALANCE SHALL INDICATE ALL EXHAUST AND
 REPLACEMENT AIR FOR THE FACILITY, PLUS THE NET
 EXFILTRATION IF APPLICABLE. THE TOTAL REPLACEMENT AIR
 AIRFLOW RATE SHALL EQUAL THE TOTAL EXHAUST AIRFLOW RATE
 PLUS THE NET EXFILTRATION.
  
 4) SUBMIT TWO COPIES OF THE NOA FOR THE RMS AC ROOF
 STAND.
  
 5) ADVISORY: SEPARATE PERMITS ARE REQUIRED FOR KITCHEN
 HOODS, FIRE SUPRESSION SYSTEMS, AND WALK IN COOLERS AND
 FREEZERS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  