Plan Review Notes
Plan Review Notes For Permit 18010561
Permit Number 18010561
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-01-25 11:31:01PERMIT # 18010561
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAIL COMMENTS:
  
 1) SHEET C-1 SHOWS COMPLIANCE WITH INCORRECT EDITION OF
 NFPA AND FLORIDA FIRE PREVENTION CODE. UPDATE THE CODE
 LIST TO REFERENCE THE 6TH EDITION OF THE FLORIDA FIRE
 PREVENTION CODE WHICH CONTAINS THE 2015 EDITION OF BOTH
 NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS. ALL WORK
 SHALL COMPLY WITH THE CURRENT EDITION.
  
 2) INDEX LISTS LIFE SAFETY PLAN UNDER SHEET 1.5. SHEET
 1.5A NOT INCLUDED, HOWEVER A SHEET 1.2A WAS LOCATED
 WITH A LIFE SAFETY PLAN DIAGRAM. UPDATE ALL SHEETS SO
 THAT THEY ARE REFLECTED PROPERLY IN THE INDEX AND THE
 ACTUAL DRAWINGS AND DRAWING NOTES.
  
 3) SHEET 1.2A - OCCUPANT LOAD CALCULATION: THERE ARE
 DISCREPANCIES REGARDING THE LISTED OCCUPANCY LOAD
 CALCULATIONS AND THE DETAILS PROVIDED IN THE DRAWING.
 EXAMPLE: DINING IS LISTED AS HAVING AN OCCUPANCY LOAD
 OF 14, HOWEVER SEATING FOR 24 IS SHOWN IN THE DRAWING.
 PLEASE REVIEW AND PROVIDE ACCURATE DETAILS AND
 EXPLANATIONS FOR DATA AND DETAILS PROVIDED.
  
 4) LOCATION OF EMERGENCY LIGHTING AND EXIT SIGNS ON
 SHEET 1.2A, DOES NOT MATCH WHAT IS PROVIDED ON SHEET
 2.1E (LIGHTING PLAN). PLEASE REVIEW AND CORRECT.
  
 5) PLEASE REVIEW AND COMPLY WITH COMMENT PROVIDED UNDER
 BUILDING PLAN REVIEW.
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  