| Plan Review Notes For Permit 18010561 |
| Permit Number |
18010561 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-01-25 11:31:01 | PERMIT # 18010561 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | FAIL COMMENTS: | | | | | | 1) SHEET C-1 SHOWS COMPLIANCE WITH INCORRECT EDITION OF | | | NFPA AND FLORIDA FIRE PREVENTION CODE. UPDATE THE CODE | | | LIST TO REFERENCE THE 6TH EDITION OF THE FLORIDA FIRE | | | PREVENTION CODE WHICH CONTAINS THE 2015 EDITION OF BOTH | | | NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS. ALL WORK | | | SHALL COMPLY WITH THE CURRENT EDITION. | | | | | | 2) INDEX LISTS LIFE SAFETY PLAN UNDER SHEET 1.5. SHEET | | | 1.5A NOT INCLUDED, HOWEVER A SHEET 1.2A WAS LOCATED | | | WITH A LIFE SAFETY PLAN DIAGRAM. UPDATE ALL SHEETS SO | | | THAT THEY ARE REFLECTED PROPERLY IN THE INDEX AND THE | | | ACTUAL DRAWINGS AND DRAWING NOTES. | | | | | | 3) SHEET 1.2A - OCCUPANT LOAD CALCULATION: THERE ARE | | | DISCREPANCIES REGARDING THE LISTED OCCUPANCY LOAD | | | CALCULATIONS AND THE DETAILS PROVIDED IN THE DRAWING. | | | EXAMPLE: DINING IS LISTED AS HAVING AN OCCUPANCY LOAD | | | OF 14, HOWEVER SEATING FOR 24 IS SHOWN IN THE DRAWING. | | | PLEASE REVIEW AND PROVIDE ACCURATE DETAILS AND | | | EXPLANATIONS FOR DATA AND DETAILS PROVIDED. | | | | | | 4) LOCATION OF EMERGENCY LIGHTING AND EXIT SIGNS ON | | | SHEET 1.2A, DOES NOT MATCH WHAT IS PROVIDED ON SHEET | | | 2.1E (LIGHTING PLAN). PLEASE REVIEW AND CORRECT. | | | | | | 5) PLEASE REVIEW AND COMPLY WITH COMMENT PROVIDED UNDER | | | BUILDING PLAN REVIEW. | | | | | | SUE ELLEN CALDERON | | | ASSISTANT FIRE MARSHAL | | | [email protected] | | | |
|