| 2018-02-07 10:42:11 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. THE NEC AND FBC SPECIFIED FOR DESIGN IS NOT THE |
| | CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE |
| | CURRENT CODE ABOVE) |
| | 2. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| | DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| | SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS |
| | (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF |
| | THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE |
| | REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| | SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1, |
| | 107.2.1 |
| | 3. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES |
| | EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN |
| | RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR |
| | LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2 |
| | 4. PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS |
| | STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT |
| | SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2 |
| | 5. RISER DIAGRAM SHOWS FOUR #3 AND ONE #8 WIRES IN A 1 |
| | INCH CONDUIT FEEDING PANEL B. THIS NUMBER AND SIZE OF |
| | WIRES EXCEEDS THE CAPACITY OF A 1 INCH CONDUIT. PROVIDE |
| | CORRECTION. NEC CHAPTER 9, TABLES 4 AND 5. |
| | 6. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| | 7. PROVIDE DETAILS OF THE METHOD OF SHUTDOWN FOR THE |
| | ELECTRICAL EQUIPMENT LOCATED UNDER THE HOOD PER NFPA |
| | 96. NFPA 96, SECTION 10.4.1, FBC 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |