Plan Review Notes
Plan Review Notes For Permit 18010561
Permit Number 18010561
Review Stop B
Sequence Number 1
Notes
Date Text
2018-01-23 07:34:002017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18010561
 ADD: 6901 OKEECHOBEE BLVD. SUITE: B-B1
 CONT: A PLUS CONSTRUCTION
 TEL: 561-267-8255
 E-MAIL: APLUSCONSTRUCTIONLLC.COM
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUESDAY JAN. 23/ 2018
 ACTION: DENIED
  
 1) THE COVERSHEET C-1 INDICATES THESE PLANS WERE
 CREATED UNDER THE 5TH EDITION OF THE FLORIDA BUILDING
 CODE. PLEASE NOTE THE 2017 EDITION (6 EDITION) OF THE
 FLORIDA BUILDING CODE WAS ADOPTED AND EFFECTIVE
 STATEWIDE ON DEC. 31/ 2017. PLEASE UPDATE THE PLANS AND
 ALL CODE REFERENCES.
  
 2) THE COVERSHEET HAS AN INDEX OF PLANS. WITHIN THE SET
 OF PLANS THERE ARE (2) SHEETS LISTED AS 1.1A OF 13 BUT
 THEY ARE 2 DIFFERENT SETS OF PLANS? DISCREPANCY IN
 PLANS. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 3) SHEET 1.0A SHOWS SECTIONS 3-6/ 1.2A WHEN YOU GO TO
 THAT SHEET THEY ARE MISSING. DISCREPANCY IN PLANS.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 4) SHEET 1.5A THE LIFE SAFETY PLAN IS MISSING.
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS: BUILDING
 7) LIFE SAFETY PLAN
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
  
 5) NONE OF THE SUBMITTED FLOOR PLANS SHOW COMPLIANCE
 WITH: COMPLIANCE WITH THE 2014 FBC-ACCESSIBILITY CODE;
 5.1) ACCESS. CODE 226.1 WHERE DINING SURFACES ARE
 PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST
 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902.
  
 5.2) 226.2 DISPERSION. DINING SURFACES AND WORK
 SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 5.3) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS.
  
 5.3))(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR
 FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 5.3))(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 6) SHEET 4.1M SHOWS NEW ROOF TOP EQUIPMENT STAND BUT IN
 THIS PLAN REVIEW CYCLE NO PRODUCT APPROVALS WERE
 SUBMITTED. PLEASE SHOW COMPLIANCE WITH: 2017 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31) (G) PRE-ENGINEERED A/C STANDS
  
 7) SHEET 4.1M. FOR ROOF TOP A/C STANDS A PRODUCT
 APPROVAL WILL BE REQUIRED (2) , REVIEWED BY THE
 DESIGNER OF RECORD. PLEASE IDENTIFY THE FOLLOWING
 REQUIREMENTS CALCULATING THE AREA (SIDE VIEW) OF THE
 ROOF TOP COMPRESSORS, CONFIGURATION ON STAND, THE MEAN
 ROOF HEIGHT OF THE STAND AND COMPRESSORS, WEIGHT,
 CIRCLED THE DESIGN PARAMETERS IN THE TABLES, ANCHORS
 AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE STAND AND
 THE STAND TO THE ROOF. THE PRODUCT APPROVAL IS TO BE
 REVIEWED BY THE DESIGNER OF RECORD, APPROVED BEFORE
 SUBMISSION TO THE BUILDING DEPARTMENT.
 W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 8) SHEET 4.1M ALSO SHOWS NEW ROOFTOP CURB AND DOWN
 UNIT. THE DETAIL INDICATES 3X3 ANGLES TO BE WELDED TO
 THE BAR JOIST, NO INFORMATION AS TO THE TYPE OF WELD,
 NOR SIZE OF WELD, OR IF CONTINUOUS. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
 WELDED OR BOLTED CONNECTIONS
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  