2018-05-22 07:08:2305/22/2018 3RD GAS REVIEW**DENIED**
  
 CONTRACTOR IS TO COME IN FOR A 1 ON 1 REVIEW BEFORE ANY
 RESUMITTAL.
  
 COMMENTS FROM LAST REVIEW:
  
 1) ANSWERED
  
 2) ANSWERED
  
 3) ANSWERED
  
 4) YOU STILL HAVE NOT PROVIDE ANY INFORMATION OR BTU
 LOAD ON THE EXISTING GAS SYSTEM THAT MUST BE INCLUDED
 FOR THIS REVIEW. 2017 FBC-RES G2413.
  
 5) ANSWERED
  
 6) ANSWERED
  
 7) SIZING CHART PROVIDE ARE DATED FROM THE 2014 CODE.
 AS OF DEC, 31,2017 WE ARE USING THE 2017 6TH ED. FUEL
 AND GAS. ALSO YOUR INLET PRESSURE AND PRESSURE DROP
 STILL LEAVES YOU AT HIGH PRESSURE ( ABOVE 12" WC) AND
 WILL REQUIRED A GAS REGULATOR. PLEASE PROVIDE CORRECTED
 SIZING CHART AND LIST GAS OUTLET METER PRESSURE AND
 PRESSURE @ TANKLESS. REFER TO TABLES FBC-RES SEC
 G24512.4, G2412.8, G2413.1, G2413.2, G2413.3. PROVIDE
 GAS REGULATOR INFORMATION AS WHILE.
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT