| 2018-05-22 07:07:48 | 05/22/2018 3RD GAS REVIEW**DENIED** | | | | | | CONTRACTOR IS TO COME IN FOR A 1 ON 1 REVIEW BEFORE ANY | | | RESUMITTAL. | | | | | | COMMENTS FROM LAST REVIEW: | | | | | | 1) ANSWERED | | | | | | 2) ANSWERED | | | | | | 3) ANSWERED | | | | | | 4) YOU STILL HAVE NOT PROVIDE ANY INFORMATION OR BTU | | | LOAD ON THE EXISTING GAS SYSTEM THAT MUST BE INCLUDED | | | FOR THIS REVIEW. 2017 FBC-RES G2413. | | | | | | 5) ANSWERED | | | | | | 6) ANSWERED | | | | | | 7) SIZING CHART PROVIDE ARE DATED FROM THE 2014 CODE. | | | AS OF DEC, 31,2017 WE ARE USING THE 2017 6TH ED. FUEL | | | AND GAS. ALSO YOUR INLET PRESSURE AND PRESSURE DROP | | | STILL LEAVES YOU AT HIGH PRESSURE ( ABOVE 12" WC) AND | | | WILL REQUIRED A GAS REGULATOR. PLEASE PROVIDE CORRECTED | | | SIZING CHART AND LIST GAS OUTLET METER PRESSURE AND | | | PRESSURE @ TANKLESS. REFER TO TABLES FBC-RES SEC | | | G24512.4, G2412.8, G2413.1, G2413.2, G2413.3. PROVIDE | | | GAS REGULATOR INFORMATION AS WHILE. | | | | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] |
|