| 2018-02-13 09:11:12 | 1ST REVIEW FBC-2014 MECHANICAL |
| | PERMIT #18010531 |
| | 2/13/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE FLORIDA BUILDING CODES SIXTH EDITION-2017 WENT |
| | INTO EFFECT ON JAN. 1, 2018. THE PERMIT APPLICATION AND |
| | PLANS FOR THE PROJECT WERE SUBMITTED AFTER THAT DATE. |
| | PLEASE UPDATE THE DESIGN CRITERIA FOR THE PROJECT |
| | INCLUDING ALL DRAWINGS, DETAILS, NOTES, ENERGY AND HVAC |
| | CALCULATIONS ETC. THAT ARE REFERENCING THE OUTDATED |
| | 2014 CODES. |
| | |
| | 2) PLEASE REMOVE THE ENERGYGAUGE SUBMITTAL FOR A SINGLE |
| | FAMILY HOME THAT HAS BEEN ATTACHED TO THE FRONT COVER |
| | OF THE PLAN AND ALSO UPDATE THE ENERGYGAUGE COMPLIANCE |
| | REPORT FOR THE NEW TENANT BUILD-OUT. |
| | |
| | 3) SHEET M-1: PROVIDE THE LEGEND AND TEXT THAT |
| | CORRELATES TO THE KEYNOTES SHOWN ON THE PLAN. |
| | |
| | 4) PROVIDE AN EXHAUST SYSTEM FOR THE PARKING GARAGE IN |
| | COMPLIANCE WITH SECTION 404.1 |
| | |
| | 5) VERIFY THE CONCEALED AREAS ABOVE THE LIBRARY, STAFF |
| | LOUNGE, HALLWAY ARE NOT BEING USED AS RETURN AIR |
| | PLENUMS- SECTION 602. |
| | |
| | 6) SUBMIT THE NOA FOR THE GRAVITY VENTILATOR AND THE |
| | CONDENSER TIE-DOWN CLIPS- RULE 9N-3 FAC. |
| | |
| | 7) PROVIDE A CONDENSATE DISPOSAL PLAN- SECTION 307. |
| | |
| | |
| | THE MECHANICAL REVIEW IS STOPPED AT THIS POINT PEMDING |
| | SUBMITTAL OF UPDATED PLANS AND CALCULATIONS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | |