| 2018-01-22 14:16:39 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THERE IS NO INDICATION OF THE OCCUPANY |
| | CLASSIFICATION AND/OR THE SEPARATION OF THE VARIOUS |
| | OCCUPANCIES OF THIS PROJECT. |
| | |
| | THOUGH BUSINESS OCCUPANCY IS INDICATED ON THE LIFE |
| | SAFETY PLAN, IT NEEDS TO BE CLARIFIED FURTHER. |
| | |
| | |
| | |
| | 2) SHEET A 1 02 - THE WALLS OF THE GARAGE/VEHICLE |
| | STORAGE AREA ARE NOT INDICATED WITH ANY FIRE RATING. |
| | |
| | THE VEHICLE GARAGE AREA IS STORAGE AND SHALL BE |
| | SEPARATED FROM THE OTHER OCCUPANCY. |
| | |
| | PER NFPA 101, CHAPTER 6, OCCUPANCY CLASSIFICATION: |
| | |
| | 6.1.14 MULTIPLE OCCUPANCIES. |
| | 6.1.14.1 GENERAL. |
| | 6.1.14.1.1 MULTIPLE OCCUPANCIES SHALL COMPLY WITH THE |
| | REQUIREMENTS OF |
| | 6.1.14.1 AND ONE OF THE FOLLOWING: |
| | (1) MIXED OCCUPANCIES ? 6.1.14.3 |
| | (2) SEPARATED OCCUPANCIES ? 6.1.14.4 |
| | |
| | 6.2 HAZARD OF CONTENTS. |
| | 6.2.1 GENERAL. |
| | 6.2.1.1 FOR THE PURPOSE OF THIS CODE, THE HAZARD OF |
| | CONTENTS SHALL BE THE RELATIVE DANGER OF THE START AND |
| | SPREAD OF FIRE, THE DANGER OF SMOKE OR GASES GENERATED, |
| | AND THE DANGER OF EXPLOSION OR OTHER OCCURRENCE |
| | POTENTIALLY ENDANGERING THE LIVES AND SAFETY OF THE |
| | OCCUPANTS OF THE BUILDING OR STRUCTURE. |
| | 6.2.1.2 HAZARD OF CONTENTS SHALL BE CLASSIFIED BY THE |
| | REGISTERED DESIGN PROFESSIONAL (RDP) OR OWNER AND |
| | SUBMITTED TO THE AUTHORITY HAVING JURISDICTION FOR |
| | REVIEW AND APPROVAL ON THE BASIS OF THE CHARACTER OF |
| | THE CONTENTS AND THE PROCESSES OR OPERATIONS CONDUCTED |
| | IN THE BUILDING OR STRUCTURE. |
| | 6.2.1.3* FOR THE PURPOSE OF THIS CODE, WHERE DIFFERENT |
| | DEGREES OF HAZARD OF CONTENTS EXIST IN DIFFERENT PARTS |
| | OF A BUILDING OR STRUCTURE, THE MOST HAZARDOUS SHALL |
| | GOVERN THE CLASSIFICATION, UNLESS HAZARDOUS AREAS ARE |
| | SEPARATED OR PROTECTED AS SPECIFIED IN SECTION 8.7 AND |
| | THE APPLICABLE SECTIONS OF CHAPTERS 11 THROUGH 43. |
| | |
| | PLEASE PROVIDE FOR THE SEPARATION OF THE GARAGE AS |
| | REQUIRED. |
| | |
| | |
| | |
| | 2) SHEET A 2 01 - THE DOUBLE DOOR,110A, IS NOT IN THE |
| | DOOR SCHEDULE AND A FIRE RATING CONSISTENT WITH THE |
| | WALL RATING IS NOT INDICATED. |
| | |
| | PLEASE PROVIDE DETAILS INCLUDING HARDWARE. |
| | |
| | |
| | |
| | 3) SHEET 2 01 - DOOR 102, AN EXIT DOOR, DOES HAVE THE |
| | HARDWARE INDICATED. |
| | |
| | PLEASE PROVIDE DETAILS CONSISTENT WITH THE REQUIRMENTS |
| | OF NFPA 101, CHAPTER 7, MEANS OF EGRESS. |
| | |
| | |
| | |
| | 4) SHEET 2 01 - DOOR 111. AN EXIT DOOR, DOES HAVE THE |
| | HARDWARE INDICATED. |
| | |
| | PLEASE PROVIDE DETAILS CONSISTENT WITH THE REQUIRMENTS |
| | OF NFPA 101, CHAPTER 7, MEANS OF EGRESS. |
| | |
| | |
| | |
| | 5) SHEET 2 01 - DOOR 100, THE FRONT DOOR, IS NOT IN THE |
| | DOOR SCHEDULE. |
| | |
| | PLEASE PROVIDE DETAILS CONSISTENT WITH THE REQUIRMENTS |
| | OF NFPA 101, CHAPTER 7, MEANS OF EGRESS. |
| | |
| | |
| | |
| | 6) SHEET S 200 - THERE IS NO DETAILS INDICATED FOR THE |
| | RAILING AND/OR GUARD. |
| | |
| | PER NFPA 101, CHAPTER 7 MEANS OF EGRESS: |
| | 7.2.2.4 GUARDS AND HANDRAILS. |
| | 7.2.2.4.1 HANDRAILS. |
| | 7.2.2.4.5.1 NEW HANDRAILS ON STAIRS SHALL BE NOT LESS |
| | THAN 34 IN. (865 MM), AND NOT MORE THAN 38 IN. (965 |
| | MM), ABOVE THE SURFACE OF THE TREAD, MEASURED |
| | VERTICALLY TO THE TOP OF THE RAIL FROM THE LEADING EDGE |
| | OF THE TREAD. |
| | 7.2.2.4.5.3 THE HEIGHT OF REQUIRED HANDRAILS THAT FORM |
| | PART OF A GUARD SHALL BE PERMITTED TO EXCEED 38 IN. |
| | (965 MM), BUT SHALL NOT EXCEED 42 IN. (1065 MM), |
| | MEASURED VERTICALLY TO THE TOP OF THE RAIL FROM THE |
| | LEADING EDGE OF THE TREAD. |
| | |
| | 7.2.2.4.6.1 THE HEIGHT OF GUARDS REQUIRED IN 7.1.8 |
| | SHALL BE MEASURED VERTICALLY TO THE TOP OF THE GUARD |
| | FROM THE SURFACE ADJACENT THERETO. |
| | 7.2.2.4.6.2 GUARDS SHALL BE NOT LESS THAN 42 IN. (1065 |
| | MM) HIGH, EXCEPT AS PERMITTED BY ONE OF THE FOLLOWING: |
| | (1) EXISTING GUARDS WITHIN DWELLING UNITS SHALL BE |
| | PERMITTED TO BE NOT LESS THAN 36 IN. (915 MM) HIGH. |
| | (2) THE REQUIREMENT OF 7.2.2.4.6.2 SHALL NOT APPLY IN |
| | ASSEMBLY OCCUPANCIES WHERE OTHERWISE PROVIDED IN |
| | CHAPTERS 12 AND 13. |
| | (3) *EXISTING GUARDS ON EXISTING STAIRS SHALL BE |
| | PERMITTED TO BE NOT LESS THAN 30 IN. (760 MM) HIGH. |
| | 7.2.2.4.6.3* OPEN GUARDS, OTHER THAN APPROVED EXISTING |
| | OPEN GUARDS, SHALL HAVE INTERMEDIATE RAILS OR AN |
| | ORNAMENTAL PATTERN SUCH THAT A SPHERE 4 IN. (100 MM) IN |
| | DIAMETER IS NOT ABLE TO PASS THROUGH ANY OPENING UP TO |
| | A HEIGHT OF 34 IN. (865 MM), AND THE FOLLOWING ALSO |
| | SHALL APPLY: |
| | (1) THE TRIANGULAR OPENINGS FORMED BY THE RISER, TREAD, |
| | AND BOTTOM ELEMENT OF A GUARDRAIL AT THE OPEN SIDE OF A |
| | STAIR SHALL BE OF SUCH SIZE THAT A SPHERE 6 IN. (150 |
| | MM) IN DIAMETER IS NOT ABLE TO PASS THROUGH THE |
| | TRIANGULAR OPENING. |
| | (2) IN DETENTION AND CORRECTIONAL OCCUPANCIES, IN |
| | INDUSTRIAL OCCUPANCIES, AND IN STORAGE OCCUPANCIES, THE |
| | CLEAR DISTANCE BETWEEN INTERMEDIATE RAILS, MEASURED AT |
| | RIGHT ANGLES TO THE RAILS, SHALL NOT EXCEED 21 IN. (535 |
| | MM). |
| | |
| | PLEASE PROVIDE DETAILS CONSISTENT WITH THE |
| | REQUIREMENTS. |
| | |
| | |
| | |
| | 7) SHEET E 3 - AN EXIT LIGHT IS SHOWN AT THE DOUBLE |
| | DOORS TO THE GARAGE. THE EXIT CAN NOT PASS THROUGH THE |
| | GARAGE. ADDITIONALLY, THE LIFE SAFETY PLAN, 3 01, SHOWS |
| | THE EXIT PATH OF TRAVEL THROUGH THE OFFICE AREA. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 8) SHEET E 3 - THERE IS NOT AN EXIT SIGN INDICATED OVER |
| | THE DOOR LEADING TO THE LIBRARY AS SHOWN FOR THE EXIT |
| | TRAVEL PATH ON THE LIFE SAFETY PLAN. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 9) SHEET E 3 - THERE IS NOT AN EXIT SIGN AT THE END OF |
| | THE CORRIDOR LEADING FROM THE CONFERENCE ROOM TO THE |
| | OPEN OFFICE AREA. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 10) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 11) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |