| 2018-01-23 06:22:15 | 2017 FBC- BUILDING/ PLAN REVIEW |
| | W. P. B. PERMIT: 18010529 |
| | ADD: 4075 HAVERHILL RD./ SUITE 4065 BAY 1 |
| | CONT: RETCOM CONSTRUCTION |
| | TEL: 561-716-3022 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. JAN. 23/ 2016 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE NOTE THE PERMIT APPLICATION INDICATES THE |
| | CREATING (2) TENANT SPACES OUT OF A SINGLE SPACE. ONLY |
| | ONE ADDRESS FOR A TENANT SPACE IS GIVEN. SINCE THERE |
| | WILL BE (2) TENANT SPACES CREATED UNDER THIS PERMIT TWO |
| | SUITE NUMBERS WILL ALSO BE REQUIRED. |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED. |
| | 2014 FBC-B 01.2 ADDRESS IDENTIFICATION. NEW AND |
| | EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED |
| | ADDRESS IDENTIFICATION. |
| | |
| | 2) CREATION OR EXTENSION OF NONCONFORMITY. 2017 |
| | EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. ALL |
| | NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. CREATION OR EXTENSION |
| | OF NONCONFORMITY. ALL NEW WORK, RE-CONFIGURATION SHALL |
| | NOT CREATE OR EXTEND ANY NONCONFORMITY IN THE EXISTING |
| | BUILDING TO WHICH THE RE-CONFIGURATION OF SPACE IS |
| | BEING MADE WITH REGARD TO ACCESSIBILITY, STRUCTURAL |
| | STRENGTH, FIRE SAFETY, MEANS OF EGRESS, OR THE CAPACITY |
| | OF MECHANICAL, PLUMBING, OR ELECTRICAL SYSTEMS. UNDER |
| | THE DEMOLITION PORTION OF THIS PROJECT THE RESTROOMS |
| | ARE BEING REMOVED. MISSING RESTROOMS NOT IN COMPLIANCE |
| | WITH: |
| | |
| | 2017 FBC-B [P]2901.1 SCOPE. THE PROVISIONS OF THIS |
| | CHAPTER AND THE FLORIDA BUILDING CODE, PLUMBING SHALL |
| | GOVERN THE ERECTION, INSTALLATION, ALTERATION, REPAIRS, |
| | RELOCATION, REPLACEMENT, ADDITION TO, USE OR |
| | MAINTENANCE OF PLUMBING EQUIPMENT AND SYSTEMS. TOILET |
| | AND BATHING ROOMS SHALL BE CONSTRUCTED IN ACCORDANCE |
| | WITH SECTION 1210. PLUMBING SYSTEMS AND EQUIPMENT SHALL |
| | BE CONSTRUCTED, INSTALLED AND MAINTAINED IN ACCORDANCE |
| | WITH THE FLORIDA BUILDING CODE, PLUMBING |
| | |
| | |
| | 3) BOTH SHEETS D-1 & A-1 UNDER THE HEADING CODE |
| | INFORMATION LIST THE JURISDICTION AS PALM BEACH COUNTY. |
| | PLEASE BE AWARE THE LOCATION OF THIS PROJECT IS UNDER |
| | THE JURISDICTION OF THE CITY OF WEST PALM BEACH, FL. |
| | PLEASE CORRECT AND UPDATE PLANS. |
| | |
| | 4) BOTH SHEETS D-1 & A-1 UNDER THE HEADING CODE |
| | INFORMATION THE PLANS INDICATE THEY ARE UNDER THE 2014 |
| | FBC. PLEASE NOTE THE FLORIDA BUILDING CODE BUILDING, |
| | 6TH EDITION (2017) EFFECTIVE DATE (ADOPTED STATEWIDE) |
| | DECEMBER 31, 2017. PLEASE UPDATE PLANS TO THE CURRENT |
| | CODE AND REFERENCES. |
| | |
| | 5) SHEET A1 INDICATES THE REMOVAL OF A PORTION OF |
| | STOREFRONT WINDOWS AND DOOR. NO WIND DESIGN CRITERIA |
| | WAS PROVIDED IN THIS SET OF PLANS. SHOW COMPLIANCE |
| | WITH: |
| | 2014 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING |
| | INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN, |
| | REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF |
| | THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE: |
| | 5.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| | VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 1609.3.1. |
| | 5.2. RISK CATEGORY. |
| | 5.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| | HEIGHT AND EXPOSURE. |
| | 5.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | 5.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF. |
| | TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. |
| | 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| | |
| | 6) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS |
| | |
| | 7) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| | RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| | MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| | PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1 |
| | INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. |
| | FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| | INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| | LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 8) W. P. B. AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1, ADMINISTRATION 107.3.4.1 PRODUCT APPROVALS. |
| | THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE |
| | 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |