2018-01-18 15:25:03THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE LINE INDICATED AS "F" AND CONNECTED TO THE FDC
 APPEARS TO RUN UNDER OR INTO THE BUILDING SLAB.
  
 THERE IS NO DETAIL INDICATED ON WHERE OR HOW THIS LINE
 "F" ATTACHED TO THE SPRINKLER SYSTEM.
  
 PLEASE PROVIDE DETAILS ON WHERE THIS FDC LINE ATTACHES
 TO THE SPRINKLER SYSTEM.
  
  
  
 2) THE LINE INDICATED AS "F" AND CONNECTED TO THE FDC
 APPEARS TO RUN UNDER OR INTO THE BUILDING SLAB.
  
 PER NFPA 13
  
 10.6 PROTECTION AGAINST DAMAGE. [24:10.6]
 10.6.1 PIPE SHALL NOT BE RUN UNDER BUILDINGS.
 [24:10.6.1]
 10.6.2 WHERE PIPE MUST BE RUN UNDER BUILDINGS, SPECIAL
 PRECAUTIONS SHALL BE TAKEN, INCLUDING THE FOLLOWING:
 (1) ARCHING THE FOUNDATION WALLS OVER THE PIPE
 (2) RUNNING PIPE IN COVERED TRENCHES
 (3) PROVIDING VALVES TO ISOLATE SECTIONS OF PIPE UNDER
 BUILDINGS [24:10.6.2]
  
  
 PLEASE REVIEW AND CORRECT OR PROVIDE JUSTIFICATIONS.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  