| Plan Review Notes For Permit 18010525 |
| Permit Number |
18010525 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-01-18 15:25:03 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THE LINE INDICATED AS "F" AND CONNECTED TO THE FDC | | | APPEARS TO RUN UNDER OR INTO THE BUILDING SLAB. | | | | | | THERE IS NO DETAIL INDICATED ON WHERE OR HOW THIS LINE | | | "F" ATTACHED TO THE SPRINKLER SYSTEM. | | | | | | PLEASE PROVIDE DETAILS ON WHERE THIS FDC LINE ATTACHES | | | TO THE SPRINKLER SYSTEM. | | | | | | | | | | | | 2) THE LINE INDICATED AS "F" AND CONNECTED TO THE FDC | | | APPEARS TO RUN UNDER OR INTO THE BUILDING SLAB. | | | | | | PER NFPA 13 | | | | | | 10.6 PROTECTION AGAINST DAMAGE. [24:10.6] | | | 10.6.1 PIPE SHALL NOT BE RUN UNDER BUILDINGS. | | | [24:10.6.1] | | | 10.6.2 WHERE PIPE MUST BE RUN UNDER BUILDINGS, SPECIAL | | | PRECAUTIONS SHALL BE TAKEN, INCLUDING THE FOLLOWING: | | | (1) ARCHING THE FOUNDATION WALLS OVER THE PIPE | | | (2) RUNNING PIPE IN COVERED TRENCHES | | | (3) PROVIDING VALVES TO ISOLATE SECTIONS OF PIPE UNDER | | | BUILDINGS [24:10.6.2] | | | | | | | | | PLEASE REVIEW AND CORRECT OR PROVIDE JUSTIFICATIONS. | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | | | | | | | |
|