| 2018-02-12 10:38:58 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. THE NEC AND FBC SPECIFIED FOR DESIGN IS NOT THE |
| | CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE |
| | CURRENT CODE ABOVE) |
| | 2. FEED FROM 150 AMP DISCONNECT TO INTERIOR PANEL IS |
| | REQUIRED TO HAVE AN EQUIPMENT GROUNDING CONDUCTOR, |
| | SIZED PER CODE. PROVIDE CORRECTION. NEC 250.122; FBC RE |
| | E3704.6, 3607.3.1 |
| | 3. ONLY ONE SERVICE PER RESIDENTIAL ADDRESS IS |
| | PERMITTED. PROVIDE CORRECTION AND/OR CLARIFICATION. FBC |
| | 107.2.1; NEC 230.2; FBC RE E3601.2 |
| | 4. PROVIDE COMPLETE RISER DIAGRAM FOR MAIN HOUSE AND |
| | SECONDARY BUILDING, SHOWING ALL DETAILS OF SERVICE |
| | EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, WIRE AND |
| | BREAKER SIZES FOR SERVICE AND FEED TO ANY SUB-PANEL(S). |
| | SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM BONDING |
| | TERMINATION POINT. NEC 215.5, 230, 250.50, 250.94, |
| | 408.30; FBC RE E3706.1, E3608.1, E3609.3; FBC 107.2.1 |
| | 5. PROVIDE LOAD CALCULATION FOR ENTIRE SERVICE, INCLUDE |
| | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| | IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2 |
| | 6. THE CURRENT AFCI NOTE DOES NOT INCLUDE ALL AREAS |
| | REQUIRED TO HAVE AFCI PROTECTION. CODE STATES: ?BRANCH |
| | CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND |
| | 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS, |
| | DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, |
| | BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| | SHALL BE AFCI PROTECTED.? ALSO, THE PANEL SCHEDULE DOES |
| | NOT REFLECT THESE REQUIREMENTS. PROVIDE CORRECTIONS. |
| | NEC 210.12, 4080.4; FBC RE E3902.16 |
| | 7. NOTE 9 STATES THAT RECEPTACLES SHALL BE TAMPER |
| | RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT |
| | APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE |
| | CORRECTION. NEC 406.12; FBC RE E4002.14 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |