Plan Review Notes
Plan Review Notes For Permit 18010516
Permit Number 18010516
Review Stop E
Sequence Number 1
Notes
Date Text
2018-01-29 16:41:31FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 SHOW ROOF LAYOUT WITH DIMENSIONS FOR ACCESS PATHS FOR
 FD.
  
 NFPA 1
  
 11.12.2.2.2 ONE- AND TWO-FAMILY DWELLINGS AND
 TOWNHOUSES
 PHOTOVOLTAIC SYSTEMS INSTALLED IN ONE- AND TWO-FAMILY
 DWELLINGS
 AND TOWNHOUSES SHALL BE IN ACCORDANCE WITH THIS
 SECTION.
  
 11.12.2.2.2.1 ACCESS AND PATHWAYS.
  
 11.12.2.2.2.1.1 HIP ROOF LAYOUTS. PHOTOVOLTAIC MODULES
 SHALL
 BE LOCATED IN A MANNER THAT PROVIDES A 3 FT (914 MM)
 WIDE
 CLEAR ACCESS PATHWAY FROM THE EAVE TO THE RIDGE OF EACH
 ROOF
 SLOPE WHERE THE PHOTOVOLTAIC MODULES ARE LOCATED. THE
 ACCESS
 PATHWAY SHALL BE LOCATED AT A STRUCTURALLY STRONG
 LOCATION OF THE
 BUILDING, SUCH AS A BEARING WALL.
  
 EXCEPTION: THE REQUIREMENT OF 11.12.2.2.2.1.1 SHALL NOT
 APPLY WHERE
 ADJOINING ROOF PLANES PROVIDE A 3 FT (914 MM) WIDE
 CLEAR ACCESS PATHWAY.
  
  
2018-01-18 09:45:29SENT TO ZONING JL
  