| Notes |
| Date |
Text |
| 2018-01-29 16:41:31 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | SHOW ROOF LAYOUT WITH DIMENSIONS FOR ACCESS PATHS FOR | | | FD. | | | | | | NFPA 1 | | | | | | 11.12.2.2.2 ONE- AND TWO-FAMILY DWELLINGS AND | | | TOWNHOUSES | | | PHOTOVOLTAIC SYSTEMS INSTALLED IN ONE- AND TWO-FAMILY | | | DWELLINGS | | | AND TOWNHOUSES SHALL BE IN ACCORDANCE WITH THIS | | | SECTION. | | | | | | 11.12.2.2.2.1 ACCESS AND PATHWAYS. | | | | | | 11.12.2.2.2.1.1 HIP ROOF LAYOUTS. PHOTOVOLTAIC MODULES | | | SHALL | | | BE LOCATED IN A MANNER THAT PROVIDES A 3 FT (914 MM) | | | WIDE | | | CLEAR ACCESS PATHWAY FROM THE EAVE TO THE RIDGE OF EACH | | | ROOF | | | SLOPE WHERE THE PHOTOVOLTAIC MODULES ARE LOCATED. THE | | | ACCESS | | | PATHWAY SHALL BE LOCATED AT A STRUCTURALLY STRONG | | | LOCATION OF THE | | | BUILDING, SUCH AS A BEARING WALL. | | | | | | EXCEPTION: THE REQUIREMENT OF 11.12.2.2.2.1.1 SHALL NOT | | | APPLY WHERE | | | ADJOINING ROOF PLANES PROVIDE A 3 FT (914 MM) WIDE | | | CLEAR ACCESS PATHWAY. | | | | | | | | 2018-01-18 09:45:29 | SENT TO ZONING JL | | | |
|