| 2018-01-19 15:39:08 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | INFORMATION: THE FLORIDA FIRE PREVENTION CODE IS NOW |
| | THE 6TH EDITION. PLEASE TAKE NOTE AND ADJUST YOUR |
| | REFERENCES AND REVIEWS ACCORDINGLY. |
| | |
| | |
| | |
| | 1) SHEET A 1 & A 2 - THE DEMO INDICATES EXISITNG 20 MIN |
| | DOORS; HOWEVER, DOOR "B" ON THE DOOR SCHULE HAS NO |
| | RATING. THESE DOORS ARE WITHIN A RATED WALL AND SHALL |
| | REFELCT THE REQUIRED RATING. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 2) SHEET A 2 & A 3 - THE DOOR SCHEDULE INDICATES THE |
| | DOOR "A" IN THE MAT COLUMN AS WD/GL. THE DIAGRAM OF |
| | DOOR "A" INDICATES ALL WOOD PANEL. |
| | |
| | PLEASE REVIEW AND CORRECT OR CLARIFY. |
| | |
| | |
| | |
| | 3) SHEET A 2 - THERE IS AN INDICATION OF DOORS "A" 180 |
| | SWING DOOR. THESE DOORS SERVE AN ELEVATOR LOBBY. IS THE |
| | EXISTING LOBBY REQUIRED TO BE RATED OR A SMOKE |
| | PARTITION. IF SO, THESE DOORS SHALL BE REQUIRED TO |
| | FUNCTION ACCORDINGLY. |
| | |
| | ADDITIONALLY, IF THE ELEVATOR SHAFT IS PRESSURIZED IT |
| | WILL AFFECT THE TYPE OF DOOR REQUIRED OF THE LOBBY. |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS AND/OR CORRECTIONS. |
| | |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |