2018-04-12 13:09:05CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE LOAD CALCULATION FOR MAIN SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
 2. PANEL B, PROVIDE GROUNDING ELECTRODE SYSTEM AS
 REQUIRED FOR A BUILDING OR STRUCTURE SUPPLIED BY A
 FEEDER OR BRANCH CIRCUIT. NEC 250.32; FBC RE3607.3
 3. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR PANEL B. NEC 225.31,
 225.32
 4. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 5. SMOKE ALARM MUST BE INSTALLED AT LEAST 3 FEET FROM
 BATHROOM DOOR. PROVIDE CORRECTION. FBC RE R314.3(4)
 6. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER, CHIEF ELECTRICAL INSPECTOR
 561-805-6742
 [email protected]
  
  