2018-04-05 15:52:08PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NEW COMMENT: A SURVEY WAS SUBMITTED, HOWEVER, THE
 PLANS INDICATE THAT THE EXISTING STORAGE STRUCTURE IS
 16' X 26' AND THE MIDDLE BUILDING ON THE SURVEY IS
 16.2' X 32'. PLEASE PROVIDE CLARIFICATION.
  
 2) (PREVIOUS COMMENT.) PROVIDE THE WINDSPEED DATA AND
 EXPOSURE CATEGORY ON THE PLANS. SPECIFY THE REQUIRED
 COMPONENT AND CLADDING DESIGN PRESSURES ON THE PLANS.
 FBC-R301.2.1
  
 3) (PREVIOUS COMMENT.) IN ORDER TO CLARIFY THE WORK
 THAT WILL BE DONE, PROVIDE AN EXISTING FLOOR PLAN AND A
 PROPOSED FLOOR PLAN. FBC 107.2.1
  
 4) (PREVIOUS COMMENT.) SPECIFY THE LEVEL OF ALTERATION
 ON THE PLANS. FBC EXISTING BUILDING CHAPTER 5. THIS
 APPEARS TO BE A LEVEL 3 ALTERATION. NEW COMMENTS: THIS
 PROJECT IS A CHANGE OF USE THAT DOES NOT INVOLVE A
 CHANGE IN OCCUPANCY CLASSIFICATION PER FBC EXISTING
 BUILDING 1001.2.1.
  
 5) COMPLIED.
  
 6) COMPLIED.
  
 7) COMPLIED.
  
 8) COMPLIED. THE ALTERATION WILL NOT CREATE ANY
 ADDITIONAL LOADS TO THE EXISTING STRUCTURE. EVALUATION
 REPORT NOT REQUIRED.
  
 9) COMPLIED. THE EXISTING WINDOWS AND DOORS WERE
 INSTALLED UNDER SEPARATE PERMIT # 91BA03568 AND
 #94008097.
  
 10) (PREVIOUS COMMENT.) FBC - R 301.2.1.2 SUBMIT TWO
 COPIES OF AN INSTALLATION SCHEDULE AND KEY PLAN FOR THE
 STORM PANELS. SPECIFY THE OPENING SIZE, THE WIND
 PRESSURES, TYPE OF ANCHOR, ANCHOR SPACING, EDGE
 DISTANCE, PANEL LENGTH, PANEL SPAN, SEPARATION DISTANCE
 FROM PANEL TO GLASS AND THE APPLICABLE SECTION NUMBER
 FROM THE INSTALLATION DRAWINGS. I HAVE INCLUDED A LINK
 TO THE CONSTRUCTION SERVICES DEPARTMENT SITE THAT HAS
 MANY OF THE RELATED FORMS INCLUDING THE SCHEDULE FOR
 INSTALLATION OF OPENING PROTECTIVE DEVICES.
 HTTP://WPB.ORG/DEVELOPMENT/FORMS-AND-PUBLICATIONS/
  
 11) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  