| 2018-04-05 15:52:08 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 2ND REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) NEW COMMENT: A SURVEY WAS SUBMITTED, HOWEVER, THE |
| | PLANS INDICATE THAT THE EXISTING STORAGE STRUCTURE IS |
| | 16' X 26' AND THE MIDDLE BUILDING ON THE SURVEY IS |
| | 16.2' X 32'. PLEASE PROVIDE CLARIFICATION. |
| | |
| | 2) (PREVIOUS COMMENT.) PROVIDE THE WINDSPEED DATA AND |
| | EXPOSURE CATEGORY ON THE PLANS. SPECIFY THE REQUIRED |
| | COMPONENT AND CLADDING DESIGN PRESSURES ON THE PLANS. |
| | FBC-R301.2.1 |
| | |
| | 3) (PREVIOUS COMMENT.) IN ORDER TO CLARIFY THE WORK |
| | THAT WILL BE DONE, PROVIDE AN EXISTING FLOOR PLAN AND A |
| | PROPOSED FLOOR PLAN. FBC 107.2.1 |
| | |
| | 4) (PREVIOUS COMMENT.) SPECIFY THE LEVEL OF ALTERATION |
| | ON THE PLANS. FBC EXISTING BUILDING CHAPTER 5. THIS |
| | APPEARS TO BE A LEVEL 3 ALTERATION. NEW COMMENTS: THIS |
| | PROJECT IS A CHANGE OF USE THAT DOES NOT INVOLVE A |
| | CHANGE IN OCCUPANCY CLASSIFICATION PER FBC EXISTING |
| | BUILDING 1001.2.1. |
| | |
| | 5) COMPLIED. |
| | |
| | 6) COMPLIED. |
| | |
| | 7) COMPLIED. |
| | |
| | 8) COMPLIED. THE ALTERATION WILL NOT CREATE ANY |
| | ADDITIONAL LOADS TO THE EXISTING STRUCTURE. EVALUATION |
| | REPORT NOT REQUIRED. |
| | |
| | 9) COMPLIED. THE EXISTING WINDOWS AND DOORS WERE |
| | INSTALLED UNDER SEPARATE PERMIT # 91BA03568 AND |
| | #94008097. |
| | |
| | 10) (PREVIOUS COMMENT.) FBC - R 301.2.1.2 SUBMIT TWO |
| | COPIES OF AN INSTALLATION SCHEDULE AND KEY PLAN FOR THE |
| | STORM PANELS. SPECIFY THE OPENING SIZE, THE WIND |
| | PRESSURES, TYPE OF ANCHOR, ANCHOR SPACING, EDGE |
| | DISTANCE, PANEL LENGTH, PANEL SPAN, SEPARATION DISTANCE |
| | FROM PANEL TO GLASS AND THE APPLICABLE SECTION NUMBER |
| | FROM THE INSTALLATION DRAWINGS. I HAVE INCLUDED A LINK |
| | TO THE CONSTRUCTION SERVICES DEPARTMENT SITE THAT HAS |
| | MANY OF THE RELATED FORMS INCLUDING THE SCHEDULE FOR |
| | INSTALLATION OF OPENING PROTECTIVE DEVICES. |
| | HTTP://WPB.ORG/DEVELOPMENT/FORMS-AND-PUBLICATIONS/ |
| | |
| | 11) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT |
| | A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| | COMMENTS HAS BEEN ADDRESSED. |
| | |