Plan Review Notes
Plan Review Notes For Permit 18010478
Permit Number 18010478
Review Stop B
Sequence Number 1
Notes
Date Text
2018-02-16 08:32:26PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) BASED ON AERIAL PHOTOS, THERE APPEARS TO BE THREE
 BUILDINGS ON THIS LOT. SUBMIT TWO COPIES OF A RECENT
 SURVEY AND SITE PLAN THAT SHOWS ALL OF THE STRUCTURES
 THAT ARE LOCATED ON THE PROPERTY. IDENTIFY THE EXISTING
 UTILITY SHED THAT WILL BE CONVERTED TO HABITABLE SPACE
 AND THE DISTANCES FROM THE SHED TO PROPERTY LINES AND
 OTHER STRUCTURES ON THE PROPERTY. FBC-R302.1
  
 2) PROVIDE THE WINDSPEED DATA AND EXPOSURE CATEGORY ON
 THE PLANS. SPECIFY THE REQUIRED COMPONENT AND CLADDING
 DESIGN PRESSURES ON THE PLANS. FBC-R301.2.1
  
 3) IN ORDER TO CLARIFY THE WORK THAT WILL BE DONE,
 PROVIDE AN EXISTING FLOOR PLAN AND A PROPOSED FLOOR
 PLAN. FBC 107.2.1
  
 4) SPECIFY THE LEVEL OF ALTERATION ON THE PLANS. FBC
 EXISTING BUILDING CHAPTER 5. THIS APPEARS TO BE A LEVEL
 3 ALTERATION.
  
 5) THE ENERGY CALCULATIONS ARE ON AN OUTDATED 2014
 FORM. THE FBC SIXTH EDITION (2017) WENT INTO EFFECT ON
 JANUARY 1, 2018. ALL NEW PERMITS APPLIED FOR ON OR
 AFTER THAT DATE ARE REQUIRED TO COMPLY WITH AND
 REFERENCE THE FBC SIXTH EDITION (2017).
  
 6) THE ENERGY CALCULATIONS SPECIFY A BEDROOM. THE CARD
 ROOM ON THE PLANS HAS A CLOSET AND APPEARS TO BE A
 BEDROOM. BEDROOMS/SLEEPING ROOMS ARE REQUIRED TO HAVE
 AN EMERGENCY ESCAPE AND RESCUE OPENING (FBC-R310) AND
 SMOKE ALARMS (FBC-R314). IF THIS ROOM WILL NOT BE USED
 AS A BEDROOM, THEN PRINT "THIS ROOM IS NOT TO BE USED
 FOR FOR SLEEPING PURPOSES" ON THE PLANS.
  
 7) THE ENERGY CALCULATIONS SPECIFY A KITCHEN. THE
 ZONING CODE DOES NOT ALLOW A KITCHEN IN THIS ACCESSORY
 STRUCTURE. CORRECT THE ENERGY CALCULATIONS AND PRINT ON
 THE PLANS THAT A KITCHEN IS NOT ALLOWED. FBC 107.2.1
  
 8) FBC EXISTING BUILDING 907.4.1 SUBMIT TWO COPIES OF
 AN ENGINEERING EVALUATION AND ANALYSIS THAT ESTABLISHES
 THE STRUCTURAL ADEQUACY OF THE ALTERED STRUCTURE SHALL
 BE PREPARED BY A REGISTERED DESIGN PROFESSIONAL AND
 SUBMITTED TO THE CODE OFFICIAL.
  
 9) UNDER PREVIOUS PERMIT
  
 10) FBC - R 301.2.1.2 SUBMIT TWO COPIES OF AN
 INSTALLATION SCHEDULE AND KEY PLAN FOR THE STORM
 PANELS. SPECIFY THE OPENING SIZE, THE WIND PRESSURES,
 TYPE OF ANCHOR, ANCHOR SPACING, EDGE DISTANCE, PANEL
 LENGTH, PANEL SPAN, SEPARATION DISTANCE FROM PANEL TO
 GLASS AND THE APPLICABLE SECTION NUMBER FROM THE
 INSTALLATION DRAWINGS. I HAVE INCLUDED A LINK TO THE
 CONSTRUCTION SERVICES DEPARTMENT SITE THAT HAS MANY OF
 THE RELATED FORMS INCLUDING THE SCHEDULE FOR
 INSTALLATION OF OPENING PROTECTIVE DEVICES.
 HTTP://WPB.ORG/DEVELOPMENT/FORMS-AND-PUBLICATIONS/
  
 11) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  