| | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | SHOW PATHWAYS ON ROOF LAYOUT. |
| | |
| | NFPA 1 |
| | |
| | 11.12.2.2.2 ONE- AND TWO-FAMILY DWELLINGS AND |
| | TOWNHOUSES |
| | PHOTOVOLTAIC SYSTEMS INSTALLED IN ONE- AND TWO-FAMILY |
| | DWELLINGS |
| | AND TOWNHOUSES SHALL BE IN ACCORDANCE WITH THIS |
| | SECTION. |
| | |
| | 11.12.2.2.2.1.1 HIP ROOF LAYOUTS. PHOTOVOLTAIC MODULES |
| | SHALL |
| | BE LOCATED IN A MANNER THAT PROVIDES A 3 FT (914 MM) |
| | WIDE |
| | CLEAR ACCESS PATHWAY FROM THE EAVE TO THE RIDGE OF EACH |
| | ROOF |
| | SLOPE WHERE THE PHOTOVOLTAIC MODULES ARE LOCATED. THE |
| | ACCESS |
| | PATHWAY SHALL BE LOCATED AT A STRUCTURALLY STRONG |
| | LOCATION OF THE |
| | BUILDING, SUCH AS A BEARING WALL. |
| | |
| | EXCEPTION: THE REQUIREMENT OF 11.12.2.2.2.1.1 SHALL NOT |
| | APPLY WHERE |
| | ADJOINING ROOF PLANES PROVIDE A 3 FT (914 MM) WIDE |
| | CLEAR ACCESS PATHWAY. |
| | |
| | |
| | 11.12.2.2.2.1.3 HIP AND VALLEY LAYOUTS. PHOTOVOLTAIC |
| | MODULES |
| | SHALL BE LOCATED NO CLOSER THAN 11?2 FT (457 MM) TO A |
| | HIP OR |
| | VALLEY IF MODULES ARE TO BE PLACED ON BOTH SIDES OF THE |
| | HIP OR |
| | VALLEY. WHERE MODULES ARE LOCATED ON ONLY ONE SIDE OF A |
| | HIP OR |
| | VALLEY OF EQUAL LENGTH, THE PHOTOVOLTAIC MODULES SHALL |
| | BE ALLOWED |
| | TO BE PLACED DIRECTLY ADJACENT TO THE HIP OR VALLEY. |
| | |
| | 11.12.2.2.2.2 RIDGE SETBACK. PHOTOVOLTAIC MODULES SHALL |
| | BE LOCATED |
| | NOT LESS THAN 3 FT (914 MM) BELOW THE RIDGE |
| | |
| 2018-01-18 09:40:15 | NEED TO ADDRESS ZONING COMMENT FOR AN ELECTRICAL |
| | REVIEW. JL |