Plan Review Notes
Plan Review Notes For Permit 18010461
Permit Number 18010461
Review Stop E
Sequence Number 1
Notes
Date Text
2018-01-29 12:10:07 
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 SHOW PATHWAYS ON ROOF LAYOUT.
  
 NFPA 1
  
 11.12.2.2.2 ONE- AND TWO-FAMILY DWELLINGS AND
 TOWNHOUSES
 PHOTOVOLTAIC SYSTEMS INSTALLED IN ONE- AND TWO-FAMILY
 DWELLINGS
 AND TOWNHOUSES SHALL BE IN ACCORDANCE WITH THIS
 SECTION.
  
 11.12.2.2.2.1.1 HIP ROOF LAYOUTS. PHOTOVOLTAIC MODULES
 SHALL
 BE LOCATED IN A MANNER THAT PROVIDES A 3 FT (914 MM)
 WIDE
 CLEAR ACCESS PATHWAY FROM THE EAVE TO THE RIDGE OF EACH
 ROOF
 SLOPE WHERE THE PHOTOVOLTAIC MODULES ARE LOCATED. THE
 ACCESS
 PATHWAY SHALL BE LOCATED AT A STRUCTURALLY STRONG
 LOCATION OF THE
 BUILDING, SUCH AS A BEARING WALL.
  
 EXCEPTION: THE REQUIREMENT OF 11.12.2.2.2.1.1 SHALL NOT
 APPLY WHERE
 ADJOINING ROOF PLANES PROVIDE A 3 FT (914 MM) WIDE
 CLEAR ACCESS PATHWAY.
  
  
 11.12.2.2.2.1.3 HIP AND VALLEY LAYOUTS. PHOTOVOLTAIC
 MODULES
 SHALL BE LOCATED NO CLOSER THAN 11?2 FT (457 MM) TO A
 HIP OR
 VALLEY IF MODULES ARE TO BE PLACED ON BOTH SIDES OF THE
 HIP OR
 VALLEY. WHERE MODULES ARE LOCATED ON ONLY ONE SIDE OF A
 HIP OR
 VALLEY OF EQUAL LENGTH, THE PHOTOVOLTAIC MODULES SHALL
 BE ALLOWED
 TO BE PLACED DIRECTLY ADJACENT TO THE HIP OR VALLEY.
  
 11.12.2.2.2.2 RIDGE SETBACK. PHOTOVOLTAIC MODULES SHALL
 BE LOCATED
 NOT LESS THAN 3 FT (914 MM) BELOW THE RIDGE
  
2018-01-18 09:40:15NEED TO ADDRESS ZONING COMMENT FOR AN ELECTRICAL
 REVIEW. JL