| 2018-05-12 08:30:13 | 1) THE GAS DRAWING REFERS TO THE 2014 FBC. THE CODE IN |
| | EFFECT FOR THIS GAS PERMIT IS THE 2017 FBC BECAUSE |
| | THESE APPLIANCES WERE SHOWN ON THE ORIGINAL PLANS AS |
| | ELECTRIC.REVISE THE NOTE ON THE PLAN. |
| | 2) THE COPIES OF THE GAS SIZING TABLES ARE FROM THE |
| | 2014 FBC. THE CODE IN EFFECT FOR THIS PERMIT IS THE |
| | 2017 FBC. SUBMIT TWO COPIES OF EACH APPLICABLE SIZING |
| | TABLE BEING USED IN THE DESIGN OF THIS GAS SYSTEM. WPB |
| | AMEND. TO FBC SEC. 107.1. |
| | 3) SUBMIT TWO COPIES OF PAGE 30 FROM THE NAVIEN |
| | INSTALLATION MANUAL THAT SHOWS THE REQUIRED LOCATION |
| | AND CLEARANCES OF THE TANKLESS WATER HEATER. WPB AMEND. |
| | TO FBC SEC. 107.1. |
| | 4) SHOW THE LOCATION OF THE GAS METERS, THE TANKLESS |
| | WATER HEATERS AND THE INLET AND OUTLET VENTS ON SHT. |
| | S-1. THE LOCATION OF THE TANKLESS WATER HEATERS AND |
| | VENTS SHALL COMPLY WITH THE INSTALLATION MANUAL. |
| | 5) THE SUBMITTED RESPONSE NARRATIVE STATES THAT A |
| | TANKLESS WATER HEATER WILL BE INSTALLED ON THE EXTERIOR |
| | OF THE BUILDING YET SHT. S-1 SHOWS A TANK TYPE WATER |
| | HEATER IN THE GARAGE AS CROSSED-OUT WITH AN "X" BUT |
| | WITH A HANDWRITTEN NOTE STATING "WATER HEATER IN |
| | GARAGE." IS THE TANK TYPE HEATER IN THE GARAGE BEING |
| | DELETED OR REMAINIING? THE RESPONSE NARRATIVE STATES " |
| | WILL WHITE OUT ON SET OF PLANS" BUT NOTHING HAS BEEN |
| | DONE. CLARIFY. |
| | 6) THE SURROUNDING AREAS ON THE SECOND FLOOR CANNOT BE |
| | USED FOR SUPPLYING COMBUSTION AIR FOR THE DRYER UNLESS |
| | LOUVERS ARE INSTALLED IN THESE ROOMS BECAUSE THERE ARE |
| | DOORS ON THESE ROOMS.THE COMMUNICATING SPACE(S) MUST BE |
| | OPEN IN ORDER TO BE USED TO COMPLY WITH SEC.G2407.5. |
| | SUBMIT INFORMATION AS TO HOW COMBUSTION AIR WILL BE |
| | SUPPLIED FOR THE DRYER. COMPLY WITH 2017 FBCR |
| | SEC.G2439.5. |
| | 7) INDICATE ON THE PLAN IF THE LAUNDRY ROOM LOUVERED |
| | BI-FOLD DOORS ARE METAL OR WOOD AND NOTE THE TOTAL |
| | SQUARE INCH AREA OF EACH OF THE LOUVERS ON EACH DOOR. |
| | THE NET FREE AREA FOR METAL LOUVERS SHALL BE ASSUMED TO |
| | BE 75% AND 25% FOR WOOD LOUVERS PER 2017 FBCR |
| | SEC.G2407.10. |
| | 8) SHOW THE LOCATION OF THE UNDERGROUND PE GAS LINE GAS |
| | ON SHT. S-1. |
| | 9) THE GAS PIPING RISER NOTES THAT THE GAS SYSTEM IS |
| | FOR A 12 INCH WATER COLUMN PRESSURE YET YOU HAVE |
| | SUBMITTED A GAS SIZING TABLE FOR PE PIPE AT A 2 PSI |
| | PRESSURE. CLARIFY AND SUBMIT A COPIES OF THE CORRECT |
| | SIZING TABLES FOR REVIEW. 2017 FBCR SEC. G2413. |
| | 10) IF THIS IS A 12 INCH WATER COLUMN SYSTEM, WHY ARE |
| | REGULATORS BEING INSTALLED? ALSO, THESE ARE SERVICE |
| | REGULATORS AND ARE USUALLY INSTALLED BY THE GAS |
| | SUPPLIER TO REDUCE AND LIMIT THE SERVICE LINE PRESSURE |
| | TO DELIVERY PRESSURE. CLARIFY THE USE OF THESE |
| | REGULATORS.WPB AMEND TO FBC SEC. 107.2.1, 2017 FBCR |
| | SEC.G2403 (DEFINITIONS). |
| | 11) THE SUBMITTED GAS SIZING TABLES FOR THE SCH. 40 |
| | METALLIC PIPE AND CSST ARE FOR A PRESSURE DROP OF 0.5 |
| | IN. W.C. BUT THE GAS PIPING RISER REFERENCES TABLES |
| | 402.4 (4) AND 402.4 (17) WHICH IS FOR A PRESSURE DROP |
| | OF 6.0 IN. W.C. CLARIFY. |
| | 12) THE SUBMITTED GAS SIZING TABLE FOR THE PE PIPE IS |
| | FOR A 2 PSI SYSTEM BUT THE SIZING TABLE REFERENCED ON |
| | THE PLAN IS 402.4 (21) WHICH IS FOR A SYSTEM LESS THAN |
| | 2 PSI WITH A PRESSURE DROP OF 0.5 IN. W.C. CLARIFY. |
| | 13) SHOW THE PIPE SIZE OF THE SCH. 40 METALLIC PIPE TO |
| | THE TANKLESS WATER HEATER AND ALSO TO THE RANGE ON BOTH |
| | GAS PIPING RISERS. IF THIS IS LESS THAN A 2 PSI SYSTEM, |
| | THE PIPE SIZE TO THE TANKLESS WATER HEATER SHALL BE A |
| | MINIMUM OF 1 INCH AND THE PIPE SIZE TO THE RANGE SHALL |
| | BE A MINIMUM OF 3/4 INCH. |
| | 14) THE SIZE OF THE SCH. 40 METALLIC PIPE ON THE POINT |
| | OF DELIVERY FROM THE METER ( OUTLET OF THE METER) SHALL |
| | BE A MINIMUM OF 1 INCH PER TABLE G2413.4 (1) OF 2017 |
| | FBCR. THE MAXIMUM BTU LOAD OF A 1 INCH PIPE AT 40 FEET |
| | FOR A LESS THAN 2 PSI SSYSTEM WITH A 0.5 IN. W.C. |
| | PRESSURE DROP IS 320,000 BTU'S AND THE SYSTEM IS |
| | SHOWING A TOTAL LOAD OF 331,000 BTU'S. CLARIFY. |
| | |