2018-03-20 16:38:0603/20/2018 GAS 2ND REVIEW**DENIED** WITH COMMENTS NOTE
 - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME
 AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED
 UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. 2ND REQUEST, SUBMIT CALCULATIONS FOR COMBUSTION AIR
 PER THE 2014 FBC-FUEL GAS CODE SEC.304.1, 614.5
 (CLOTHES DRYERS) OR 2017 FBC-RES. SEC. G 2407.1 AND
 G2439.4 (CLOTHES DRYERS).
 2. 2ND REQUEST, SUBMIT TWO COPIES OF A HOUSE PLAN
 SHOWING THE LOCATION OF THE TANKLESS WATER HEATER AND
 THE LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR
 WINDOWS IN RELATION TO THE WATER HEATER. THE LOCATION
 OF THE WATER HEATER SHALL COMPLY WITH THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE WATER
 HEATER IS SHOWN AS A TANK ON PLAN BUT NOT DRAWN OUTSIDE
 AND NO DISTANCE GIVEN FROM WINDOW OR DOOR. ON THE
 ISOMETRIC, YOU HAVE IT OUTSIDE. THE PLAN CAN BE HAND
 DRAWN IN. IF THE HEATER IS GOING TO BE IN THE GARAGE
 HOW ARE YOU GOING TO VENT IT OUTSIDE, PLEASE CLARIFY?
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 3. 2ND REQUEST SUBMIT MANUFACTURER?S SPECIFICATIONS FOR
 THE PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. PLEASE PROVIDE DOCUMENTATION FROM THE
 MANUFACTURER THAT THE REGULATORS ARE APPROVED FOR
 EXTERIOR USE. 2017 FGC SEC.410.1
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  