Plan Review Notes
Plan Review Notes For Permit 18010387
Permit Number 18010387
Review Stop B
Sequence Number 1
Notes
Date Text
2018-01-23 18:27:43PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS HAVE SEVERAL REFERENCES TO THE 2014 FBC.
 THE FBC SIXTH EDITION (2017) WENT INTO EFFECT ON
 JANUARY 1, 2018. ALL NEW PERMITS APPLIED FOR ON OR
 AFTER THAT DATE ARE REQUIRED TO COMPLY WITH AND
 REFERENCE THE FBC SIXTH EDITION AND NEC 2014.
  
 2) THE $5,000.00 VALUE FOR THE SPA APPEARS TO BE LOW.
 SUNBMIT A COPY OF THE SIGNED CONTRACT TO VERIFY THE
 VALUE. FBC 109.3 BUILDING PERMIT VALUATION. FOR
 PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS
 SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 3) YOU WILL NEED TO SUBMIT ANOTHER APPLICATION FOR A
 POOL PLUMBING SUB PERMIT SO THAT YOU CAN GET A PERMIT
 NUMBER TO USE WHEN SCHEDULING THE POOL PLUMBING
 INSPECTIONS.
  
  