Plan Review Notes
Plan Review Notes For Permit 18010380
Permit Number 18010380
Review Stop E
Sequence Number 1
Notes
Date Text
2018-01-24 15:57:56CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE NEC AND FBC SPECIFIED FOR DESIGN IS NOT THE
 CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE
 CURRENT CODE ABOVE)
 2. ELECTRICAL NOTE S DOES NOT COVER ALL AREAS REQUIRED
 TO HAVE AFCI PROTECTION. PER CODE: "BRANCH CIRCUITS
 THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS, DINING
 ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED." PROVIDE CORRECTION. NEC
 210.12; FBC RE E3902.16
 3. RISER DIAGRAM DOES NOT MATCH WHAT PLAN SHOWS. RISER
 HAS A METER TO A PANEL, WHILE THE PLAN SHOWS A METER TO
 AN OUTSIDE DISCONNECT FEEDING AN INTERIOR PANEL.
 PROVIDE CORRECTION. FBC 107.2.1; NEC 215.5
 4. PROVIDE GFCI PROTECTED RECEPTACLE ON 2ND FLOOR
 BALCONY. NEC 210.52(E); FBC RE E3901.7
 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 6. A GFCI PROTECTED OUTLET ON A 20 AMP CIRCUIT IS
 REQUIRED WITHIN 3 FEET OF EACH BASIN. MASTER BATH DOES
 NOT SHOW THIS. PROVIDE CORRECTION. NEC 210.11(C)(3),
 210.52(D); FBC RE E3703.4, E3901.6
 7. PROVIDE GFCI PROTECTION FOR OUTLETS ON THE KITCHEN
 ISLAND. NEC 210.8, 210.52(C)(2); FBC RE E3901.4.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER