2018-01-31 18:56:58PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS HAVE SEVERAL REFERENCES TO THE FBC FIFTH
 EDITION (2014). THE FBC SIXTH EDITION (2017) WENT INTO
 EFFECT ON JANUARY 1, 2018. ALL NEW PERMITS APPLIED FOR
 ON OR AFTER THAT DATE ARE REQUIRED TO COMPLY WITH AND
 REFERENCE THE FBC SIXTH EDITION (2017).
  
 2) THE MASTER BATHROOM ON THE SECOND FLOOR WAS
 INCREASED IN SIZE AND NOW CONTAINS A WINDOW THAT IS
 ADJACENT TO THE SHOWER. FBC-R 308.4.5 REQUIRES THE
 WINDOW TO HAVE SAFETY GLAZING OR TO BE LARGE MISSILE
 IMPACT RATED.
  
 3) ONE OF THE WINDOWS IN THE REMODELED BEDROOM 2 ON THE
 SECOND FLOOR IS NOW LOCATED IN THE ENLARGED MASTER
 BATHROOM. THIS BEDROOM IS REQUIRED TO MAINTAIN THE SAME
 LEVEL OF EGRESS THAT IT HAD BEFORE THE REMODELING. THE
 CLEAR OPENING AREA IN THE REMAINING WINDOW MUST BE
 EQUAL TO WHAT EXISTING BEFORE THE CHANGES. FBC EXISTING
 BUILDING 702.5
  
 4) THE PLANS INDICATE THAT A NEW GAS RANGE IS BEING
 INSTALLED. SHOW COMPLIANCE WITH FBC-R315 FOR REQUIRED
 CARBON MONOXIDE ALARMS.
  