| Plan Review Notes For Permit 18010380 |
| Permit Number |
18010380 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-01-31 18:56:58 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE PLANS HAVE SEVERAL REFERENCES TO THE FBC FIFTH | | | EDITION (2014). THE FBC SIXTH EDITION (2017) WENT INTO | | | EFFECT ON JANUARY 1, 2018. ALL NEW PERMITS APPLIED FOR | | | ON OR AFTER THAT DATE ARE REQUIRED TO COMPLY WITH AND | | | REFERENCE THE FBC SIXTH EDITION (2017). | | | | | | 2) THE MASTER BATHROOM ON THE SECOND FLOOR WAS | | | INCREASED IN SIZE AND NOW CONTAINS A WINDOW THAT IS | | | ADJACENT TO THE SHOWER. FBC-R 308.4.5 REQUIRES THE | | | WINDOW TO HAVE SAFETY GLAZING OR TO BE LARGE MISSILE | | | IMPACT RATED. | | | | | | 3) ONE OF THE WINDOWS IN THE REMODELED BEDROOM 2 ON THE | | | SECOND FLOOR IS NOW LOCATED IN THE ENLARGED MASTER | | | BATHROOM. THIS BEDROOM IS REQUIRED TO MAINTAIN THE SAME | | | LEVEL OF EGRESS THAT IT HAD BEFORE THE REMODELING. THE | | | CLEAR OPENING AREA IN THE REMAINING WINDOW MUST BE | | | EQUAL TO WHAT EXISTING BEFORE THE CHANGES. FBC EXISTING | | | BUILDING 702.5 | | | | | | 4) THE PLANS INDICATE THAT A NEW GAS RANGE IS BEING | | | INSTALLED. SHOW COMPLIANCE WITH FBC-R315 FOR REQUIRED | | | CARBON MONOXIDE ALARMS. | | | |
|