| 2018-01-17 10:14:15 | 1ST REVIEW FBC-2017 MECHANICAL , WPB AMENDMENTS TO THE |
| | FBC. |
| | PERMIT #18010377 |
| | 1/17/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE DESIGN PROFESSIONAL IN RESPOSNSIBLE CHARGE |
| | (ENGINEER OR ARCHITECT OF RECORD) FOR THE MAIN PROJECT |
| | SHALL PROVIDE A SHOP DRAWING APPROVAL STAMP ON THE |
| | UNDERGROUND EXHAUST SYSTEM PLANS- SECTION 107.3.4.1 WPB |
| | AMENDMENTS TO THE FBC. |
| | |
| | 2) THE DETAILS, NOTES, AND DATA TABLES ON THE PLAN NEED |
| | TO BE ENLAREGED FOR REVIEW AND FOR PUBLIC RECORD |
| | KEEPINGL- SECTION 107.2.1.4 WPB AMENDMENTS TO THE FBC. |
| | |
| | 3) INDICATE THE TYPE AND SIZE OF UNDERGROUND EXHAUST |
| | DUCT TO BE INSTALLED AND THE BURIAL DEPTH- SECTION |
| | 603.8. VERIFY THE DUCT MEETS ASTM D 2412 STANDARDS- |
| | SECTION 603.8.3. |
| | |
| | 4) INDICATE THE BLOWER EXHAUST DISCHARGE IS A MINIMUM |
| | 10' FROM GRADE, 10' FROM OPERABLE OPENINGS INTO THE |
| | BUILDING, AND 10' FROM PROPERTY LINES- SECTION 501.3.1. |
| | |
| | 5) PROVIDE WIND LOAD ENGINEERING FOR ATTACHMENT OF THE |
| | BLOWERS TO THE EXTERIOR OF THE BUILDING- SECTION |
| | 301.15. PLEASE SEE SECTION 1609 FBC-14 BUILDING FOR |
| | WIND DESIGN CRITERIA. |
| | |
| | 6) PROVIDE AN ELECTRICAL PLAN AND SUB-PERMIT. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |