Plan Review Notes
Plan Review Notes For Permit 18010377
Permit Number 18010377
Review Stop M
Sequence Number 1
Notes
Date Text
2018-01-17 10:14:151ST REVIEW FBC-2017 MECHANICAL , WPB AMENDMENTS TO THE
 FBC.
 PERMIT #18010377
 1/17/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE DESIGN PROFESSIONAL IN RESPOSNSIBLE CHARGE
 (ENGINEER OR ARCHITECT OF RECORD) FOR THE MAIN PROJECT
 SHALL PROVIDE A SHOP DRAWING APPROVAL STAMP ON THE
 UNDERGROUND EXHAUST SYSTEM PLANS- SECTION 107.3.4.1 WPB
 AMENDMENTS TO THE FBC.
  
 2) THE DETAILS, NOTES, AND DATA TABLES ON THE PLAN NEED
 TO BE ENLAREGED FOR REVIEW AND FOR PUBLIC RECORD
 KEEPINGL- SECTION 107.2.1.4 WPB AMENDMENTS TO THE FBC.
  
 3) INDICATE THE TYPE AND SIZE OF UNDERGROUND EXHAUST
 DUCT TO BE INSTALLED AND THE BURIAL DEPTH- SECTION
 603.8. VERIFY THE DUCT MEETS ASTM D 2412 STANDARDS-
 SECTION 603.8.3.
  
 4) INDICATE THE BLOWER EXHAUST DISCHARGE IS A MINIMUM
 10' FROM GRADE, 10' FROM OPERABLE OPENINGS INTO THE
 BUILDING, AND 10' FROM PROPERTY LINES- SECTION 501.3.1.
  
 5) PROVIDE WIND LOAD ENGINEERING FOR ATTACHMENT OF THE
 BLOWERS TO THE EXTERIOR OF THE BUILDING- SECTION
 301.15. PLEASE SEE SECTION 1609 FBC-14 BUILDING FOR
 WIND DESIGN CRITERIA.
  
 6) PROVIDE AN ELECTRICAL PLAN AND SUB-PERMIT.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  