| 2018-03-28 08:02:48 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 18010368 |
| | ADD: 2481 OKEECHOBEE BLVD. |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: 561-822-7650 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: WED. MARCH 28, 2018 |
| | ACTION: DENIED. |
| | |
| | 1)PROVISO: DEFERRED SUBMITTAL / 2017 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| | ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| | 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, INTAKE AND EXHAUST |
| | FANS & ROOF TOP VENTILATORS |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 2) PROVISO: PLEASE IDENTIFY ON THE PRODUCT APPROVAL |
| | BEFORE SUBMITTING TO DESIGNER OF RECORD AND BEFORE |
| | SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS |
| | WITH GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & |
| | HEIGHT, TYPE OF GLAZING, MULLION SIZE, LENGTH IF |
| | UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED, |
| | ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING |
| | SIZE. 2014 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND |
| | DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED |
| | MANUFACTURERS INSTRUCTIONS. FASTENER SIZE AND SPACING |
| | SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE |
| | CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN |
| | THE TESTS. |
| | |
| | 3)PROVISO: ROOFING: FOR ALL ROOFING PRODUCTS PLEASE |
| | IDENTIFY ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED |
| | PRESSURES FOR ROOF ZONE # 1. REVIEW THE PRODUCT |
| | APPROVAL LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED |
| | FOR ROOF ZONES 2 & 3. FASTENER DENSITIES SHALL BE |
| | INCREASED FOR BOTH INSULATION & THE BASE SHEET AS |
| | CALCULATED IN COMPLIANCE WITH ROOFING APPLICATION |
| | STANDARDS RAS 117. CALCULATION PREPARED, SIGNED AND |
| | SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR |
| | REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. |
| | |
| | 4)PROVISO: SHEET S-403 DETAIL # 1 SHOW A NEW MECHANICAL |
| | STAND WITH A VERTICAL DISTANCE MEASURED 48 INCHES FROM |
| | THE TOP OF THE BAR JOIST TO THE BOTTOM OF THE |
| | CONDENSING UNIT. THE 2017 FBC-B TABLE 1510.10 STATES |
| | CLEARANCE BELOW RAISED ROOF MOUNTED MECHANICAL UNITS. |
| | FOR A UNIT 60 INCHES IN WIDTH OR WIDER THERE IS TO BE |
| | 48 INCHES OF CLEARANCE. THE WAY THE DISTANCE IS |
| | MEASURED YOU DO NOT HAVE 48 INCHES CLEARANCE. |
| | DEFINITION: THE DISTANCE BY WHICH ONE OBJECT CLEARS |
| | ANOTHER OR THE CLEAR SPACE BETWEEN THEM. |
| | |
| | 5) PROVISO: THE S-403 DETAIL 1 NOR THE H DRAWINGS SHOW |
| | HOW THE ROOF TOP CONDENSERS ARE GOING TO BE ANCHORED TO |
| | RESIST SLIDING OR THE MOMENT OF OVERTURNING. 2017 FBC-B |
| | 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL MEMBERS AND |
| | THEIR CONNECTIONS SHALL BE DETERMINED BY METHODS OF |
| | STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT EQUILIBRIUM, |
| | GENERAL STABILITY, GEOMETRIC COMPATIBILITY AND BOTH |
| | SHORT- AND LONG-TERM MATERIAL PROPERTIES. EVERY |
| | STRUCTURE SHALL BE DESIGNED TO RESIST THE OVERTURNING |
| | EFFECTS CAUSED BY THE LATERAL FORCES SPECIFIED IN THIS |
| | CHAPTER. SEE SECTION 1609 FOR WIND LOADS. |
| | |
| | 6-8) COMPLIED. |
| | |
| | 9) THE RESPONSE INDICATED THE TENANT WOULD LIKE A |
| | RESIDENT INSPECTOR ON SITE FOR THE STEEL AND CONCRETE |
| | WORK. FORMS WERE E-MAILED TO: |
| | [email protected] CAME BACK UNDELIVERABLE |
| | [email protected] 3/27/2018 04:46 PM |
| | |
| | FORMS NEED TO BE SIGNED AND RETURNED BEFORE PERMIT |
| | ISSUANCE. |
| | |
| | ONLY (2) SETS OF PLANS WERE SUBMITTED, (3) SETS |
| | REQUIRED FOR RESIDENT INSPECTOR!!!!!!! |
| | |
| | 10) COMPLIED. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |