| 2018-02-12 10:45:52 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18010368 |
| | 2/12/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET H-101: PROVIDE THE TYPE AND SIZE OF THE NEW |
| | DUCTWORK- NOTE H2. |
| | |
| | 2) H-101: PROVIDE AND AIR DEVICE SCHEDULE. |
| | |
| | 3) H-101: NOTES H1 AND H5 ARE IN CONFLICT. NOTE H1 |
| | SPECIFIES PAINTED DUCTWORK HOWEVER NOTE H5 INDICATES |
| | THE DUCTS TO BE INSULATED. PLEASE NOTE FIBERGLASS |
| | INSULATION AND/OR FIREGLASS DUCTWORK SHALL NOT BE |
| | PAINTED PER THE UL LISTINGS AND FLAMESPEAD |
| | SMOKE-DEVELOPED INDEX OF THE MATERAL. |
| | |
| | 4) PROVIDE SUPPORT AND HANGING DETAILS FOR THE NEW |
| | DUCTWORK PER SMACNA HVAC DUCT CONSTRUCTION STANDARDS- |
| | 2005. |
| | |
| | 5) COMCHECK REPORT: PROVIDE COMPLIANCE DATA FOR THE |
| | HVAC ALTERATIONS. |
| | |
| | 6) ADVISORY: THE ARCHITECTURAL AND ELECTRICAL PLANS ARE |
| | SHOWING ALERATIONS TO THE REFRIGERATIONS SYTEMS. PLEASE |
| | NOTE THAT THE CITY OF WEST PALM BEACH REQUIRES A |
| | SEPARATE PERMIT FOR REFRIGERATION SYSTEMS FOR FOOD |
| | CASES, WALK-IN BOXES ETC. COMPLETE PLANS AND |
| | SPECIFICATIONS MUST BE SUBMITTED. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |