| 2018-02-14 13:44:21 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES |
| | EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN |
| | RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR |
| | LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2 |
| | 2. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| | DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| | SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND |
| | SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN |
| | THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE |
| | INDICATING THE REQUIRED SEPARATE PERMITS AND DATA |
| | SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE SYSTEMS |
| | PRESENT. FBC 105.1, 107.2.1 |
| | 3. ELECTRICAL LOAD SUMMARY STATES THAT NEC 220.87 IS |
| | USED TO DETERMINE EXISTING LOAD. PROVIDE THE 12 MONTH |
| | HISTORY TO CONFIRM STATED DEMAND LOAD ON PLAN. FBC |
| | 107.2.1, NEC 220.87 |
| | 4. ELECTRICAL LOAD SUMMARY SHOWS THAT A TOTAL OF 65.2 |
| | KVA IS BEING ADDED TO PANEL DP1. THE PANEL SCHEDULE |
| | SHOWS A LOAD OF 101.52 KVA FOR CDRU AND 47.1 KVA FOR |
| | REMOTE DEFROST PANEL, WHICH WOULD BE A TOTAL OF 148.62 |
| | KVA, PLUS OTHER ADDITIONAL LOADS FROM THE SUMMARY |
| | TOTALING 12.3 KVA, FOR A GRAND TOTAL OF 160.92 KVA. |
| | THIS WOULD OVERLOAD THE EXISTING PANEL AND TRANSFORMER |
| | FEEDING PANEL DP1. PROVIDE CLARIFICATION AND/OR |
| | CORRECTION. NEC 215.2, 220, 408.30: FBC 107.2.1 |
| | 5. PROVIDE LOAD CALCULATION FOR 400 AMP, 3 PHASE, |
| | 277/480 VOLT SYSTEM. ARE THERE ANY LOADS BEING FED FROM |
| | THIS AHEAD OF THE TRANSFORMER FOR PANEL DP1? IF NOT, |
| | DISREGARD THIS REQUEST. NEC 215.2, 220, 408.30: FBC |
| | 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |