| 2018-01-17 13:24:31 | 1ST REVIEW FBC-2017 RESIDENTIAL MECHANICAL, ENERGY |
| | CONSERVATION CODES. |
| | PERMIT #18010366 |
| | 1/17/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE SUBMITTED ENERGYGAUGE FORM R405-2014 IS |
| | OUTDATED. THE 2017 FLORIDA BUILDING CODE- ENERGY |
| | CONSERVATION, SIXTH EDITION IS EFFRECT AS OF JAN. 1, |
| | 2017. PLEASE PROVIDE AN UPDATED COMPLIANCE SUBMITTALS |
| | AND SEE BELOW: |
| | |
| | R503.2 CHANGE IN SPACE CONDITIONING. |
| | |
| | ANY NONCONDITIONED OR LOW-ENERGY SPACE THAT IS ALTERED |
| | TO BECOME CONDITIONED SPACE SHALL BE REQUIRED TO BE |
| | BROUGHT INTO FULL COMPLIANCE WITH THIS CODE. |
| | |
| | EXCEPTION: WHERE THE SIMULATED PERFORMANCE OPTION IN |
| | SECTION R405 IS USED TO COMPLY WITH THIS SECTION, THE |
| | ANNUAL ENERGY COST OF THE PROPOSED DESIGN IS PERMITTED |
| | TO BE 110 PERCENT OF THE ANNUAL ENERGY COST OTHERWISE |
| | ALLOWED BY SECTION R405.3. |
| | |
| | 2) THE CFM DISTRIBUTION AND DUCT SIZING ON PLANS DOES |
| | NOT MATCH THE SPECIFICATIONS LISTED UNDER THE "SUPPLY |
| | BRANCH DETAIL TABLE" IN THE AC CALCULATIONS- PLEASE |
| | CORRECT. IN ADDITION, BEDROOM 1-A IS NOT SHOWN ON THE |
| | PLAN AS |
| | |
| | 3) THE TRANSFER GRILLS ARE UNDERSIZED PER SECTION |
| | M1602.3 FBC-17 RESIDENTIAL- 50 SQ. INCHES PER 100 CFM |
| | REQUIRED. |
| | |
| | 4) PROVIDE CONDENSER PAD AND CONDENSER MOUNTING DETAILS |
| | IN COMPLIANCE WITH SECTIONS M1305.1.4.1 AND M1401.4 |
| | |
| | 5) PLEASE PROVIDE THE AC EQUIPMENT SCHEDULE ON THE |
| | PLAN. |
| | |
| | 6) PROVIDE AN ELECTRICAL PLAN AND A SUB-PERMIT. |
| | |
| | 7) ONE COPY OF THE LEVEL 1 AC PLAN IS MISSING. PLEASE |
| | PROVIDE A DUPLICATE COPY. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |