| Plan Review Notes For Permit 18010354 |
| Permit Number |
18010354 |
|
| Review Stop |
G |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2018-05-19 09:25:20 | 1) THERE IS STILL ONE COPY OF THE PROPANE TANK | | | INSTALLATION DETAIL SHEET THAT BEARS A COPY OF THE | | | ENGINEER'S SEAL AND SIGNATURE. YOU HAVE SUBMITTED | | | COPIES OF A SIGNED AND SEALED DOCUMENT BY A LICENSED | | | ENGINEER ( KEVIN L.ATCHLEY) FOR THE PROPANE TANK | | | HOLDOWN DETAILS.FOR THE 5TH TIME, DOCUMENTS BEARING AN | | | ENGINEER'S SEAL AND SIGNATURE MUST BE ORIGINAL AND | | | CANNOT BE COPIES PER THE FL. ADMIN. CODE RULE | | | 61G15-23.001. IF YOU ARE GOING TO SUBMIT THESE DETAILS, | | | ENSURE THAT THEY ARE SIGNED AND SEALED BY THE ENGINEER | | | OF RECORD. | | | 2) THERE IS ONLY ONE COPY OF THE AMERICAST GENERATOR | | | CONCRETE PAD DRAWING THAT HAS AN ORIGINAL ENGINEER'S | | | SEAL AND SIGNATURE. SUBMIT ANOTHER COPY THAT BEARS AN | | | ORIGINAL SEAL AND SIGNATURE OF THE DESIGN PROFESSIONAL | | | OF RECORD PER FL. ADMIN. CODE 61G15-23.001. | | | 3) THERE IS ONLY ONE COPY OF THE MANUFACTURER'S | | | SPECIFICATIONS FOR THE GENERATOR. SUBMIT TWO COPIES OF | | | THE MANUFACTURER'S SPECIFICATIONS FOR THE GENERATOR. | | | WPB AMEND. TO FBC SEC. 107.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | | | | | | | |
|