| Plan Review Notes For Permit 18010354 |
| Permit Number |
18010354 |
|
| Review Stop |
G |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2018-05-04 10:25:24 | 1) YOU HAVE SUBMITTED COPIES OF A SIGNED AND SEALED | | | DOCUMENT BY A LICENSED ENGINEER ( KEVIN L.ATCHLEY) FOR | | | THE PROPANE TANK HOLDOWN DETAILS. DOCUMENTS BEARING AN | | | ENGINEER'S SEAL AND SIGNATURE MUST BE ORIGINAL AND | | | CANNOT BE COPIES PER THE FL. ADMIN. CODE RULE | | | 61G15-23.001. IF YOU ARE GOING TO SUBMIT THESE DETAILS, | | | ENSURE THAT THEY ARE SIGNED AND SEALED BY THE ENGINEER | | | OF RECORD. | | | 2) THERE IS ONLY ONE COPY OF THE AMERICAST GENERATOR | | | CONCRETE PAD DRAWING, THE ELECTRICAL DRAWING AND THE | | | MANUFACTURER'S SPECIFICATIONS FOR THE GENERATOR. SUBMIT | | | TWO COPIES OF THE SIGNED AND SEALED GENERATOR PAD | | | DRAWING AND OF THE ELECTRICAL PLANS AND THE | | | MANUFACTURER'S SPECIFICATIONS FOR THE GENERATOR. WPB | | | AMEND. TO FBC SEC. 107.1. | | | 3) INDICATE THE TYPE OF PIPE AND THE PIPE SIZE | | | DOWNSTREAM OF THE SECOND STAGE REGULATOR. INDICATE THE | | | PSI OF THE SYSTEM DOWNSTREAM OF THE SECOND REGULATOR. |
|