Plan Review Notes
Plan Review Notes For Permit 18010354
Permit Number 18010354
Review Stop G
Sequence Number 2
Notes
Date Text
2018-03-06 05:48:341) THE ENGINEER WHOSE COPY OF HIS SIGNATURE AND SEAL
 FOR THE DOCUMENTS FROM TIE DOWN ENGINEERING HAS A
 LICENSE THAT HAS BEEN NULL AND VOID SINCE 2/28/15. ALSO
 SIGNATURE IS REQUIRED TO BE WET AND SEAL CANNOT BE
 COPIED. COPIES ARE NOT PERMITTED PER FL.ADMIN CODE
 61G15-23.001
  
 2) IN ADDITION TO COMMENT #1, YOU HAVE ALSO SUBMITTED
 COPIES OF A SIGNED AND SEALED DOCUMENT BY A LICENSED
 ENGINEER (CARMO ENGINEERING ASSOCIATES) FOR THE PROPANE
 TANK HOLDOWN DETAILS. AGAIN, DOCUMENTS BEARING AN
 ENGINEER'S SEAL AND SIGNATURE MUST BE ORIGINAL AND
 CANNOT BE COPIES PER THE FL. ADMIN. CODE RULE
 61G15-23.001.THE PRINTING ON THESE DOCUMENTS IS
 ILLEGIBLE. IF YOU ARE GOING TO SUBMIT THESE DETAILS,
 ENSURE THAT THEY ARE SIGNED AND SEALED BY THE ENGINEER
 OF RECORD AND ARE LEGIBLE.
  
 3) THERE ARE TWO DIFFERENT SHEETS THAT HAVE BEEN
 SUBMITTED FOR THE CATHODIC PROTECTION. ONE IS
 ILLEGIBLE. REMOVE THE SPECIFICATION SHEET FOR THE
 CATHODIC PROTECTION THAT WILL NOT BE USED. FBC107.2.1.
 A CATHODIC PROTECTION SYSTEM SHALL BE REQUIRED PER NFPA
 58 SECS. 5.2.1.11, 6.6.6.1 (I) AND SHALL BE MONITORED
 PER NFPA 58 SEC.6.6.6.1 (J). SUBMIT DETAILS ON THE TYPE
 OF CATHODIC PROTECTION, SIZE ( LBS) & NUMBER OF
 MAGNESIUM BAG(S), SIZE & TYPE OF ANODE CABLE.
  
 4) SOME OF THE MANIFACTURER'S SPECIFICATION SHEETS FOR
 THE PRESSURE REGULATORS ARE ILLEGIBLE. SUBMIT TWO
 COPIES OF CLEAR AND LEGIBLE REGULATOR SPECIFICATIONS
 FOR REVIEW WPB AMEND. TO FBC SEC. 107.2.1. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION. 2017 FGC SEC.410.1.
  
 5) YOU HAVE SUBMITTED A SIZING TABLE FOR THE SCHEDULE
 40 METALLIC PIPE FROM THE 2014 FBC-FUEL GAS CODE. THE
 CODE IN EFFECT FOR THIS PERMIT IS THE 2017 FBC-FUEL GAS
 CODE. SUBMIT TWO COPIES OF THE SIZING TABLE FROM THE
 2017 FBC-FUEL GAS CODE.
  
 6) THE SIZING TABLE FROM NFPA 58 FOR THE 10 PSI IS
 ALMOST ILLEGIBLE. SUBIT TWO LEGIBLE COPIES OF THE
 SIZING TABLE. WPB AMEND. TO FBC SEC. 107.2.1.
  
 7) THERE ARE NOW 3 DIFFERENT TANK TIE-DOWN DETAILS
 SUBMITTED WITH THIS REVIEW. I HAVE NO IDEA WHICH DETAIL
 IS GOING TO BE USED. REMOVE ALL DOCUMENTS FROM THIS
 PACKAGE THAT ARE NOT APPLICABLE AND SUBMIT TWO COPIES
 OF TANK TIE-DOWN DETAILS. IF THE TIE-DOWN DETAILS TO BE
 SUBMITTED BEAR AN ENGINEER'S SEAL AND SIGNATURE, THEY
 MUST BE ORIGINAL AND NOT COPIES. FL. ADMIN. CODE RULE
 61G15-23.001.
  
 8) THE GAS DRAWING SHOWING THE 500 GAL. UNDERGROUND
 TANK HAS A NOTE THAT REFERS TO SEC.411.1 OF THE
 FBC-FUEL GAS CODE. THIS CODE SECTION REFERS TO
 APPLIANCE CONNECTIONS AND MANUFACTURED HOMES. CLARIFY.
  
 I SUGGEST YOU CONTACT THIS PLAN REVIEWER TO ARRANGE A
 MEETING TO GO OVER THE REVIEW COMMENTS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692