| 2018-03-06 05:48:34 | 1) THE ENGINEER WHOSE COPY OF HIS SIGNATURE AND SEAL |
| | FOR THE DOCUMENTS FROM TIE DOWN ENGINEERING HAS A |
| | LICENSE THAT HAS BEEN NULL AND VOID SINCE 2/28/15. ALSO |
| | SIGNATURE IS REQUIRED TO BE WET AND SEAL CANNOT BE |
| | COPIED. COPIES ARE NOT PERMITTED PER FL.ADMIN CODE |
| | 61G15-23.001 |
| | |
| | 2) IN ADDITION TO COMMENT #1, YOU HAVE ALSO SUBMITTED |
| | COPIES OF A SIGNED AND SEALED DOCUMENT BY A LICENSED |
| | ENGINEER (CARMO ENGINEERING ASSOCIATES) FOR THE PROPANE |
| | TANK HOLDOWN DETAILS. AGAIN, DOCUMENTS BEARING AN |
| | ENGINEER'S SEAL AND SIGNATURE MUST BE ORIGINAL AND |
| | CANNOT BE COPIES PER THE FL. ADMIN. CODE RULE |
| | 61G15-23.001.THE PRINTING ON THESE DOCUMENTS IS |
| | ILLEGIBLE. IF YOU ARE GOING TO SUBMIT THESE DETAILS, |
| | ENSURE THAT THEY ARE SIGNED AND SEALED BY THE ENGINEER |
| | OF RECORD AND ARE LEGIBLE. |
| | |
| | 3) THERE ARE TWO DIFFERENT SHEETS THAT HAVE BEEN |
| | SUBMITTED FOR THE CATHODIC PROTECTION. ONE IS |
| | ILLEGIBLE. REMOVE THE SPECIFICATION SHEET FOR THE |
| | CATHODIC PROTECTION THAT WILL NOT BE USED. FBC107.2.1. |
| | A CATHODIC PROTECTION SYSTEM SHALL BE REQUIRED PER NFPA |
| | 58 SECS. 5.2.1.11, 6.6.6.1 (I) AND SHALL BE MONITORED |
| | PER NFPA 58 SEC.6.6.6.1 (J). SUBMIT DETAILS ON THE TYPE |
| | OF CATHODIC PROTECTION, SIZE ( LBS) & NUMBER OF |
| | MAGNESIUM BAG(S), SIZE & TYPE OF ANODE CABLE. |
| | |
| | 4) SOME OF THE MANIFACTURER'S SPECIFICATION SHEETS FOR |
| | THE PRESSURE REGULATORS ARE ILLEGIBLE. SUBMIT TWO |
| | COPIES OF CLEAR AND LEGIBLE REGULATOR SPECIFICATIONS |
| | FOR REVIEW WPB AMEND. TO FBC SEC. 107.2.1. REGULATORS |
| | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| | APPROVED FOR OUTDOOR INSTALLATION. 2017 FGC SEC.410.1. |
| | |
| | 5) YOU HAVE SUBMITTED A SIZING TABLE FOR THE SCHEDULE |
| | 40 METALLIC PIPE FROM THE 2014 FBC-FUEL GAS CODE. THE |
| | CODE IN EFFECT FOR THIS PERMIT IS THE 2017 FBC-FUEL GAS |
| | CODE. SUBMIT TWO COPIES OF THE SIZING TABLE FROM THE |
| | 2017 FBC-FUEL GAS CODE. |
| | |
| | 6) THE SIZING TABLE FROM NFPA 58 FOR THE 10 PSI IS |
| | ALMOST ILLEGIBLE. SUBIT TWO LEGIBLE COPIES OF THE |
| | SIZING TABLE. WPB AMEND. TO FBC SEC. 107.2.1. |
| | |
| | 7) THERE ARE NOW 3 DIFFERENT TANK TIE-DOWN DETAILS |
| | SUBMITTED WITH THIS REVIEW. I HAVE NO IDEA WHICH DETAIL |
| | IS GOING TO BE USED. REMOVE ALL DOCUMENTS FROM THIS |
| | PACKAGE THAT ARE NOT APPLICABLE AND SUBMIT TWO COPIES |
| | OF TANK TIE-DOWN DETAILS. IF THE TIE-DOWN DETAILS TO BE |
| | SUBMITTED BEAR AN ENGINEER'S SEAL AND SIGNATURE, THEY |
| | MUST BE ORIGINAL AND NOT COPIES. FL. ADMIN. CODE RULE |
| | 61G15-23.001. |
| | |
| | 8) THE GAS DRAWING SHOWING THE 500 GAL. UNDERGROUND |
| | TANK HAS A NOTE THAT REFERS TO SEC.411.1 OF THE |
| | FBC-FUEL GAS CODE. THIS CODE SECTION REFERS TO |
| | APPLIANCE CONNECTIONS AND MANUFACTURED HOMES. CLARIFY. |
| | |
| | I SUGGEST YOU CONTACT THIS PLAN REVIEWER TO ARRANGE A |
| | MEETING TO GO OVER THE REVIEW COMMENTS. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |