| 2018-01-19 15:34:28 | 01/19/2018 GAS 1ST REVIEW**DENIED** |
| | |
| | 1) ENGINEER FOR TIE DOWN ENGINEERING LICENSE |
| | REVOKE/EXPIRED. ALSO SIGNATURE IS REQUIRED TO BE WET. |
| | COPIES ARE NOT PERMITTED PER FL.ADMIN CODE 61G15-23.001 |
| | |
| | 2) CATHADIC PROTECTIONSPEC SHEET NOT LEGIBLE. |
| | FBC107.2.1.A CATHODIC PROTECTION SYSTEM SHALL BE |
| | REQUIRED PER NFPA 58 SECS. 5.2.1.11, 6.6.6.1 (I) AND |
| | SHALL BE MONITORED PER NFPA 58 SEC.6.6.6.1 (J). SUBMIT |
| | DETAILS ON THE TYPE OF CATHODIC PROTECTION, SIZE (LBS) |
| | & NUMBER OF MAGNESIUM BAG(S), SIZE & TYPE OF ANODE |
| | CABLE. |
| | |
| | 3) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION. 2017 FGC SEC.410.1 |
| | |
| | 4) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE |
| | APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS TABLE 402.4 |
| | (28) FOR THE PROPER PIPE SIZE AND BTU LOAD |
| | |
| | 5) SUBMIT SIZING CHART FOR THE .5 SCH 40 METAL |
| | PIPING.SUBMIT TWO COPIES OF THE APPLICABLE SIZING |
| | TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON |
| | THE PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) |
| | FROM THE GAS CODE OR OTHER STANDARD THAT WERE USED IN |
| | THE DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014 |
| | FBC-FUEL GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES |
| | 402.4 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. |
| | G2412.4, G2412.8, G2413.1, G2413.2, & G2413.3 |
| | |
| | TIM HUNT |
| | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER |
| | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | 561-805-6695 |
| | [email protected] |
| | |