2018-01-23 18:01:491ST REVIEW FBC-2014 MECHANICAL
 REVISION #18010314
 MASTER #17010099
 1/23/18
  
 1) SHEET M104: A FIRE DAMPER IS SHOWN WHERE THE 48X16
 DUCT PENETRATES THE WALL AT THE STORAGE ROOM, HOWEVER
 THE NOTE IS INDICATING THE WALL IS "NO LONGER RATED"-
 PLEASE CLARIFY THE NEED FOR THE FIRE DAMPER, AND
 PROVIDE REVISED ARCHITECTURAL DRAWINGS THAT CLEARLY
 INDICATE WHICH WALLS ARE FIRE-RATED AND WHICH ARE NOT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  