| Plan Review Notes For Permit 18010302 |
| Permit Number |
18010302 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-01-11 18:14:57 | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS. | | | CODE: FBC 6TH EDITION (2017) | | | | | | 1- WIND LOAD CALCULATIONS SUBMITTED ARE MARKED WITH THE | | | DESIGN PRESSURES FOR AN INTERIOR ZONE IN EXPOSURE "B". | | | ACCORDING TO SEC. R301.2.1.4 FBC-RESIDENTIAL, THIS | | | BUILDING IS LOCATED IN EXPOSURE "C" NOT EXPOSURE. | | | REVISE AS REQUIRED. OR PROVIDE COMPLETE ENGINEERING | | | ANALYSIS WITH CALCULATIONS FOR ALL WIND DIRECTIONS. | | | | | | 2- PROVIDE PRODUCT APPROVAL THAT MEETS THE DESIGN | | | PRESSURES FOR EXPOSURE "C". DRAWINGS SUBMITTED WITH | | | FLORIDA PRODUCT APPROVAL FL17347-R2 DON'T MEET THOSE | | | DESIGN PRESSURES. | | | FAC 61G20-3.001 | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|