| 2018-03-15 10:07:03 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 2ND REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE |
| | ENERGY FORM R405-2017. FBC ENERGY CONSERVATION |
| | R103.1.1.2 |
| | |
| | 2) THE ICP POLYSET RTA-1, ROOF TILE ADHESIVE THAT WAS |
| | SUBMITTED (NOA NO. 16-0315.03) IS NOT ONE OF THE |
| | APPROVED ADHESIVES THAT IS LISTED IN THE ENTEGRA ROOF |
| | TILE NOA NO. 1--0421.08. THE RTA-1 PRODUCT APPROVAL |
| | STATES THAT IT CAN BE USED WITH ANY ROOF TILE ASSEMBLY |
| | HAVING A CURRENT NOA THAT LISTS ATTACHMENT RESISTANCE |
| | VALUES WITH ITS USE. THIS TILE NOA DOES NOT LIST IT. |
| | SUBMIT TWO SETS OF PRODUCT APPROVALS FOR A ROOF TILE |
| | ADHESIVE THAT IS APPROVED FOR USE WITH THE TILE. FBC |
| | 107.3.4 & FAC 61G20-3.001 |
| | |
| | 3) THE WINDOW SCHEDULE SPECIFIES DOUBLE HUNG WINDOWS |
| | AND THE PRODUCT APPROVALS THAT WERE SUBMITTED ARE FOR |
| | SINGLE HUNG WINDOWS. PLEASE COORDINATE THE PRODUCT |
| | APPROVALS WITH THE PLANS. FBC 107.2.1 (REPEAT COMMENT) |
| | |
| | 4) THE PLANS REQUIRE DESIGN PRESSURES OF +47.8 AND |
| | -59.31 FOR THE SECTIONAL GARAGE DOORS. THE MAXIMUM |
| | DESIGN LOADS LISTED IN PRODUCT APPROVALS FOR THE |
| | SECTIONAL GARAGE DOORS IS +46 AND -52 PSF WHICH DO NOT |
| | MEET THE REQUIRED DESIGN PRESSURES. FBC-R301.2.1.1 |
| | NOTE: TABLE R301.2(4) IN THE FBC RESIDENTIAL HAS LOWER |
| | DESIGN PRESSURE FOR GARAGE DOORS. (REPEAT COMMENT) |
| | |
| | 5) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A |
| | RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| | COMMENTS HAS BEEN ADDRESSED. |
| | |
| | |
| | |
| | |