| Plan Review Notes For Permit 18010292 |
| Permit Number |
18010292 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-01-12 12:50:00 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | THE PREVENTION BUREAU SUPPORTS EMERGENCY REPAIRS, | | | HOWEVER: | | | | | | 1) SIMPLY PROVIDEING SPEC SHEETS IS INSUFFICIENT FOR | | | DOCUMENTING THIS PROPOSED PROJECT. | | | | | | | | | 2) PROVIDE A SCOPE OF WORK FOR CLARIFICATION PURPOSES. | | | IS THE PUMP CURRENTLY WORKING? IS A FIRE WATCH | | | CURRENTLY IMPLEMENTED? | | | | | | PROVIDE HOW LONG THE FIRE PUMP WILL BE DONE AND WHAT | | | EFFORTS ARE BEING TAKEN TO PROTECT THE BUILDING DURING | | | THAT TIME, I.E FIRE WATCH , IF APPLICABLE. | | | | | | | | | 3) PROVIDE A FLOOR LAYOUT, LOCATION AND EQUIPMENT | | | IDENTIFICATIONS. | | | | | | | | | 4) PROVIDE THE APPLICABLE FIRE CODE REFERENCES FOR | | | COMPLIANCE PURPOSES, I.E. NFPA 20, NFPA 110, NFPA 70, | | | ETC. | | | | | | | | | 5) A SUITE NUMBER #200, IS INDICATED ON THE | | | APPLICATION. IS THIS THE PUMP ROOM NUMBER ? | | | | | | PLEASE CLARIFIY OR CORRECT. | | | | | | | | | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|