Plan Review Notes
Plan Review Notes For Permit 18010211
Permit Number 18010211
Review Stop P
Sequence Number 2
Notes
Date Text
2018-03-29 12:06:1703/29/2018 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. HOT WATER HEATER DRAIN PAN REQUIRED IN THE DWELLING
 AT LOCATION WHERE WATER LEAKAGE FROM THE TANK WILL
 CAUSE DAMAGE FBC R 2801.6 REQUIRED PAN.
 2. THE PAN DRAIN SHALL EXTEND FULL-SIZE AND TERMINATE
 OVER A SUITABLY LOCATED INDIRECT WASTE RECEPTOR OR
 SHALL EXTEND TO THE EXTERIOR OF THE BUILDING AND
 TERMINATE NOT LESS THAN 6 INCHES FBC R P2801.6.2 PAN
 DRAIN TERMINATION.
 3. THERMAL EXPANSION DEVICE FOR CONTROLLING INCREASED
 PRESSURE CAUSED BY THERMAL EXPANSION SHALL BE INSTALLED
 WHERE REQUIRED IN ACCORDANCE WITH SECTIONS FBC R
 2903.4.1.
 4. WATER HEATER SHOWN ON PAGES A102 AND A103 AS A
 SINGLE UNIT BUT ON E101 AND P101 IT SHOWS TWO UNITS,
 PLEASE LABEL AND CLARIFY IF TWO UNITS ARE TO BE USED.
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW