| Plan Review Notes For Permit 18010211 |
| Permit Number |
18010211 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-01-30 09:58:45 | RESIDENTIAL (R3) ALTERATION, MECHANICAL REVIEW | | | COMMENTS. | | | CODE: FBC 6TH EDITION (2017). | | | | | | 1- LAYOUT SHOWN ON DRAWING M101 DOESN'T MATCH LAYOUT | | | SHOWN ON PROPOSED FLOOR PLAN ON SHEET A102. SEE MASTER | | | BEDROOM LAYOUT AND REVISE AS REQUIRED TO MATCH. SEC. | | | 107.2.1 CITY AMENDMENTS. | | | | | | 2- BASED ON THE PROPOSED FLOOR PLAN ON SHEET A102 THE | | | MASTER BEDROOM DOESN'T COMPLY WITH THE BALANCED RETURN | | | AIR SEC. M1602.3 FBC-RESIDENTIAL, 5TH EDITION (2017). | | | REVISE AS REQUIRED SHOWING COMPLIANCE. | | | | | | 3- PROVIDE COMPLETE A/C EQUIPMENT SPECIFICATIONS ON | | | PLAN. SEC. 107.3.5.3 CITY AMENDMENTS | | | | | | ******PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | | COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. | | | *****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD | | | DRAWINGS. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD | | | DRAWINGS FOR REFERENCE TO HELP EXPEDITE THE REVIEW | | | PROCESS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|