Plan Review Notes
Plan Review Notes For Permit 18010211
Permit Number 18010211
Review Stop M
Sequence Number 1
Notes
Date Text
2018-01-30 09:58:45RESIDENTIAL (R3) ALTERATION, MECHANICAL REVIEW
 COMMENTS.
 CODE: FBC 6TH EDITION (2017).
  
 1- LAYOUT SHOWN ON DRAWING M101 DOESN'T MATCH LAYOUT
 SHOWN ON PROPOSED FLOOR PLAN ON SHEET A102. SEE MASTER
 BEDROOM LAYOUT AND REVISE AS REQUIRED TO MATCH. SEC.
 107.2.1 CITY AMENDMENTS.
  
 2- BASED ON THE PROPOSED FLOOR PLAN ON SHEET A102 THE
 MASTER BEDROOM DOESN'T COMPLY WITH THE BALANCED RETURN
 AIR SEC. M1602.3 FBC-RESIDENTIAL, 5TH EDITION (2017).
 REVISE AS REQUIRED SHOWING COMPLIANCE.
  
 3- PROVIDE COMPLETE A/C EQUIPMENT SPECIFICATIONS ON
 PLAN. SEC. 107.3.5.3 CITY AMENDMENTS
  
 ******PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
 *****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWINGS. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD
 DRAWINGS FOR REFERENCE TO HELP EXPEDITE THE REVIEW
 PROCESS.
  