Plan Review Notes
Plan Review Notes For Permit 18010211
Permit Number 18010211
Review Stop B
Sequence Number 1
Notes
Date Text
2018-01-26 18:59:53RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: FBC 6TH EDITION (2017).
  
 1- SHEET A101:
 A) ALL PERMIT APPLICATIONS SUBMITTED AFTER JANUARY 1ST
 OF 2018 ARE ENFORCED WITH THE CURRENT CODE FBC 6TH
 EDITION (2017). REVISE CODE DATA TO REFLECT THE CURRENT
 CODE 2017 EDITION NOT 2014. CHAPTER 553 F.S.
  
 B) BASED ON THE SCOPE OF WORK SHOWN ON PLANS THIS IS
 ALTERATION LEVEL 3, NOT ALTERATION LEVEL 2. REVISE AS
 REQUIRED. SEC. 505 FBC-EXISTING BUILDING, 6TH EDITION
 (2017).
  
 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R501.1.1 FBC-ENERGY CONSERVATION, 6TH EDITION (2017).
  
 3- IT LOOKS LIKE THE SPECIFIED BEDROOM WINDOWS MAY NOT
 COMPLY WITH THE MINIMUM CLEAR WIDTH OPENING REQUIRED
 FOR EMERGENCY ESCAPE AND RESCUE OPENINGS. CLEARLY
 PROVIDE COMPLIANCE WITH THE EGRESS REQUIREMENTS FOR
 BEDROOM #2 AND DRESSING ROOM (FORMER BEDROOM #3).
 SPECIFY ACTUAL SIZE OF PROPOSED WINDOW AND PROVIDE
 MANUFACTURER'S SPECIFICATIONS SHOWING THAT THE PROPOSED
 SIZE COMPLIES WITH THE EGRESS REQUIREMENTS. SEC. 702.5
 FBC-EXISTING BUILDING.
 NOTE: CLEARLY SPECIFY EXISTING WINDOW TYPE AND SIZE.
 AND SPECIFY EXISTING ROUGH OPENING TO VERIFY COMPLIANCE
 WITH THE EGRESS REQUIREMENTS.
  
 4- SHEET A103: NOTE ON CEILING PLAN FOR BEDROOM #2
 SPECIFY EXISTING CEILING JOISTS TO BE REPLACED. PROVIDE
 SPECIFICATIONS FOR CEILING JOIST AND STRUCTURAL
 CONNECTORS. SEC. R301.1 FBC-RESIDENTIAL.
  
 5- FRONT DOOR WOOD BUCK INFILL DETAIL ON SHEET A501:
 CLEARLY SPECIFY SIZE OF OF TAPCON. SEC. R301.1
 FBC-RESIDENTIAL.
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) ENTRY DOOR SIZE AS SHOWN ON PLANS.
 NOTE: NEED PRODUCT APPROVAL FOR 2017 CODE VERSION.
  
 B) FAMILY ROOM FRENCH DOOR. NEED PRODUCT APPROVAL FOR
 2017 CODE VERSION. FLORIDA PRODUCT APPROVAL FL7347-R5
 SUBMITTED IS FOR 2014 CODE VERSION, IT'S FOR DOUBLE
 DOORS ONLY AND DOESN'T MEET THE DESIGN PRESSURES
 CALCULATED BY THE ARCHITECT OF RECORD. . NEED PRODUCT
 APPROVAL FOR 2017 CODE VERSION THAT MEETS THE
 CALCULATED DESIGN PRESSURES AND FOR SINGLE DOOR AS
 SHOWN ON PLANS.
  
 C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. NOTE: PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR OR ARCHITECT OF RECORD TO LIST THE FLORIDA
 PRODUCT APPROVAL NUMBER NEXT TO EACH SPECIFIED
 CONNECTOR.
  
 7- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 8- WINDOW MULLION PRODUCT APPROVAL SUBMITTED: CLEARLY
 SPECIFY MULLION SIZE TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES. SEC. R301.1 FBC-RESIDENTIAL.
  
 ******PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
 *****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWINGS. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD
 DRAWINGS FOR REFERENCE TO HELP EXPEDITE THE REVIEW
 PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]