2018-01-12 06:42:18****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. PLEASE PROVIDE TWO IDENTICAL COLLATED SETS OF
 DOCUMENTS FOR PERMIT ISSUANCE. THE TWO "FORM 100" ARE
 MARKED DIFFERENTLY; CHECK ALL.
  
 2. THE APPROVED ASSEMBLY SELECTED DOES NOT MEET THE
 ENHANCED FASTENING REQUIREMENTS OF ZONES 2 & 3 FOR THE
 FLAT DECK. SEE LAST PAGE OF THE NOA, GENERAL LIMITATION
 #7, ENGINEERING IS REQUIRED.
  
 PLEASE NOTE THAT SOME OF THE DOCUMENTS SUBMITTED ARE
 FROM PALM BEACH COUNTY'S ROOF POLICY. THE JURSIDICTION
 FOR THIS PROJECT IS THE CITY OF WEST PALM BEACH. IF YOU
 WISH TO AVOID ENGINEERING FOR A TWO SQUARE ROOF, THERE
 ARE OTHER PRODUCT APPROVALS ON THE MARKET WHICH DO
 INCLUDE ASSEMBLIES WHICH MEET THE DESIGN PRESSURES;
 PLEASE CONTACT YOUR ROOF SUPPLIER OR TECHNICAL
 REPRESENTATIVE FOR OPTIONS.
  
  