2018-01-23 13:08:281ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18010205
 1/23/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PERMIT VALUE IS BASED ON LABOR, MATERIALS,
 EQUIPMENT, DESIGN FEES, PROFIT AMD OVERHEAD- SECTION
 109.3 WPB AMENDMENTS TO THE FBC. THE APPLICATION AND
 CONTRACT INDICATES THE $1,011.15 VALUE LISTED ON THE
 PERMIT APPLICATION IS FOR LABOR ONLY. PLEASE ADJUST THE
 VALUE IN ACCORDINGLY.
  
 2) PROVIDE A FLOOR PLAN DRAWING THAT SHOW THE LOCATION
 OF THE VENTLESS HOOD.
  
 3) CLARIFY HOW MAKEUP AIR IS BEING PROVIDED FOR THE
 3000 CFM EXHAUST HOOD. SHOW THE SOURCE OF THE MAKEUP
 AIR ON THE PLAN AND PROVIDE AIR BALANCE CALCULATIONS.
  
 4) REFER TO SECTION 508.1.1 MAKEUP AIR TEMPERATURE AND
 SHOW COMPLIANCE: THE TEMPERATURE DIFFERENTIAL BETWEEN
 MAKEUP AIR AND THE AIR IN THE CONDITIONED SPACE SHALL
 NOT EXCEED 10?F (6?C) EXCEPT WHERE THE ADDED HEATING
 AND COOLING LOADS OF THE MAKEUP AIR DO NOT EXCEED THE
 CAPACITY OF THE HVAC SYSTEM.
  
 5) PLEASE NOTE THAT THE RESTAURANT PLANS UNDER PRIMARY
 PERMIT #17010872 INDICATES A VENTED HOOD WITH AN
 EXHAUST RATE OF 1500 CFMS. PLEASE ALERT THE GENERAL
 CONTRACTOR THAT REVISION TO THE MAIN PLAN WILL BE
 REQUIRED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  