| 2018-01-23 13:08:28 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18010205 |
| | 1/23/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PERMIT VALUE IS BASED ON LABOR, MATERIALS, |
| | EQUIPMENT, DESIGN FEES, PROFIT AMD OVERHEAD- SECTION |
| | 109.3 WPB AMENDMENTS TO THE FBC. THE APPLICATION AND |
| | CONTRACT INDICATES THE $1,011.15 VALUE LISTED ON THE |
| | PERMIT APPLICATION IS FOR LABOR ONLY. PLEASE ADJUST THE |
| | VALUE IN ACCORDINGLY. |
| | |
| | 2) PROVIDE A FLOOR PLAN DRAWING THAT SHOW THE LOCATION |
| | OF THE VENTLESS HOOD. |
| | |
| | 3) CLARIFY HOW MAKEUP AIR IS BEING PROVIDED FOR THE |
| | 3000 CFM EXHAUST HOOD. SHOW THE SOURCE OF THE MAKEUP |
| | AIR ON THE PLAN AND PROVIDE AIR BALANCE CALCULATIONS. |
| | |
| | 4) REFER TO SECTION 508.1.1 MAKEUP AIR TEMPERATURE AND |
| | SHOW COMPLIANCE: THE TEMPERATURE DIFFERENTIAL BETWEEN |
| | MAKEUP AIR AND THE AIR IN THE CONDITIONED SPACE SHALL |
| | NOT EXCEED 10?F (6?C) EXCEPT WHERE THE ADDED HEATING |
| | AND COOLING LOADS OF THE MAKEUP AIR DO NOT EXCEED THE |
| | CAPACITY OF THE HVAC SYSTEM. |
| | |
| | 5) PLEASE NOTE THAT THE RESTAURANT PLANS UNDER PRIMARY |
| | PERMIT #17010872 INDICATES A VENTED HOOD WITH AN |
| | EXHAUST RATE OF 1500 CFMS. PLEASE ALERT THE GENERAL |
| | CONTRACTOR THAT REVISION TO THE MAIN PLAN WILL BE |
| | REQUIRED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |