| 2018-01-10 17:01:39 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THERE IS NO BUILDING AND KITCHEN LAY-OUT PLAN |
| | INDICATING WHERE THIS UNIT IS PROPOSED. |
| | |
| | PLEASE PROVIDE EXACT LOCATION INCLUDING DIMENSIONS. |
| | |
| | |
| | 2) THERE IS NO INDICATION WHERE THE REMOTE |
| | ACTIVATION/PULL STATION IS LOCATED. |
| | |
| | 10.5 MANUAL ACTIVATION. |
| | 10.5.1 A READILY ACCESSIBLE MEANS FOR MANUAL ACTIVATION |
| | SHALL BE LOCATED BETWEEN 1067 MM AND 1219 MM (42 IN. |
| | AND 48 IN.) ABOVE THE FLOOR, BE ACCESSIBLE IN THE EVENT |
| | OF A FIRE, BE LOCATEDIN A PATH OF EGRESS, AND CLEARLY |
| | IDENTIFY THE HAZARD PROTECTED. |
| | 10.5.1.1 AT LEAST ONE MANUAL ACTUATION DEVICE SHALL BE |
| | LOCATED A MINIMUM OF 3 M (10 FT) AND A MAXIMUM OF 6 M |
| | (20 FT) FROM THE PROTECTED HOOD EXHAUST SYSTEM(S) |
| | WITHIN A PATH OF EGRESS OR AT AN ALTERNATIVE LOCATION |
| | ACCEPTABLE TO THE AHJ. |
| | |
| | PLEASE PROVIDE EXACT LOCATION INCLUDING DIMENSIONS. |
| | |
| | |
| | |
| | |
| | 3) THERE IS NO INDICATION OF FUEL OF ELECTRICAL |
| | SHUTOFF. |
| | |
| | 10.4 FUEL AND ELECTRIC POWER SHUTOFF. |
| | 10.4.1 UPON ACTIVATION OF ANY FIRE-EXTINGUISHING SYSTEM |
| | FOR A COOKING OPERATION, ALL SOURCES OF FUEL AND |
| | ELECTRICAL POWER THAT PRODUCE HEAT TO ALL EQUIPMENT |
| | REQUIRING PROTECTION BY THAT SYSTEM SHALL AUTOMATICALLY |
| | SHUT OFF. |
| | |
| | PLEASE PROVIDE SPECIFIC DETAILS. |
| | |
| | |
| | |
| | 4) THERE IS NO INDICATION OF FIRE ALARM CONNECTION FOR |
| | ACTIVATION OR TIE-INTO THE FIRE ALARM SYSTEM BY A |
| | CERTIFIED CONTRACTOR. |
| | |
| | 10.6 SYSTEM ANNUNCIATION. |
| | 10.6.1 UPON ACTIVATION OF AN AUTOMATIC |
| | FIRE-EXTINGUISHING SYSTEM, AN AUDIBLE ALARM OR VISUAL |
| | INDICATOR SHALL BE PROVIDED TO SHOW THAT THE SYSTEM HAS |
| | ACTIVATED. |
| | 10.6.2 WHERE A FIRE ALARM SIGNALING SYSTEM IS SERVING |
| | THE OCCUPANCYWHERE THE EXTINGUISHING SYSTEM IS LOCATED, |
| | THE ACTIVATION OF THE AUTOMATIC FIRE-EXTINGUISHING |
| | SYSTEM SHALL ACTIVATE THE FIRE ALARM SIGNALING SYSTEM. |
| | |
| | PLEASE PROVIDE SPECIFIC DETAILS. |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |