| Plan Review Notes For Permit 18010196 |
| Permit Number |
18010196 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-01-10 05:18:48 | 01/10/2018 GAS 1ST REVIEW**DENIED** | | | | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | ALSO WE ARE CURRENTLY USING THE 2017 6TH ED OF THE | | | FLORIDA FUEL AND GAS. | | | | | | YOU DID NOT INCLUDE ANY MANUFACTURE SPECS OR | | | INSTALLATION MANUAL FOR THE GENERATOR. CURRENTLY WE DO | | | NOT SHOW ANY PERMIT OR APPLICATION FOR A PERMIT TO | | | INSTALL A GENERATOR. SUBMIT MANUFACTURERS SPECIFICATION | | | SHEETS / INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO | | | VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND | | | FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014 | | | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED | | | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS | | | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF | | | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1 OR YOU | | | WILL NEED TO WAIT FOR THE MAIN GENERATOR PERMIT BEFORE | | | YOUR SUB CAN BE ISSUED. | | | | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] | | | | | | | | | | | | |
|