Plan Review Notes
Plan Review Notes For Permit 18010196
Permit Number 18010196
Review Stop G
Sequence Number 1
Notes
Date Text
2018-01-10 05:18:4801/10/2018 GAS 1ST REVIEW**DENIED**
  
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
 ALSO WE ARE CURRENTLY USING THE 2017 6TH ED OF THE
 FLORIDA FUEL AND GAS.
  
 YOU DID NOT INCLUDE ANY MANUFACTURE SPECS OR
 INSTALLATION MANUAL FOR THE GENERATOR. CURRENTLY WE DO
 NOT SHOW ANY PERMIT OR APPLICATION FOR A PERMIT TO
 INSTALL A GENERATOR. SUBMIT MANUFACTURERS SPECIFICATION
 SHEETS / INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1 OR YOU
 WILL NEED TO WAIT FOR THE MAIN GENERATOR PERMIT BEFORE
 YOUR SUB CAN BE ISSUED.
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  
  
  
  